15
■
2 - indoor units in operation A + B
Indoor Unit
SAP – K91GJA (
✕
2)
Outdoor Unit
SAP – CM1821GA
230 V Single phase 50 Hz
g
RATING CAPACITY
5.20 kW
EVAPORATOR
CONDENSER
ENT. TEMP. °C
OUTDOOR AMBIENT TEMP. °C
W.B.
D.B.
20
25
30
35
40
43
TC
5.24
5.01
4.78
4.56
4.28
3.94
CM
1.29
1.39
1.49
1.60
1.79
2.00
21
SHC
3.52
3.40
3.28
3.17
3.03
2.87
15
23
SHC
3.94
3.82
3.70
3.59
3.45
3.29
25
SHC
4.36
4.24
4.12
4.01
3.87
3.71
27
SHC
4.78
4.66
4.54
4.43
4.28
3.94
29
SHC
5.20
5.01
4.78
4.56
4.28
3.94
31
SHC
5.24
5.01
4.78
4.56
4.28
3.94
TC
5.62
5.38
5.13
4.89
4.59
4.23
CM
1.32
1.43
1.53
1.64
1.84
2.04
21
SHC
3.09
2.97
2.85
2.74
2.60
2.44
17
23
SHC
3.51
3.39
3.27
3.16
3.02
2.86
25
SHC
3.93
3.81
3.69
3.58
3.44
3.28
27
SHC
4.35
4.23
4.11
4.00
3.86
3.69
29
SHC
4.77
4.65
4.53
4.42
4.28
4.11
31
SHC
5.19
5.07
4.95
4.84
4.59
4.23
TC
5.98
5.72
5.46
# 5.20
4.89
4.50
CM
1.36
1.47
1.58
1.69
1.90
2.10
21
SHC
2.64
2.52
2.40
2.29
2.15
1.99
19
23
SHC
3.06
2.94
2.82
2.71
2.57
2.41
25
SHC
3.48
3.36
3.24
3.13
2.99
2.83
27
SHC
3.90
3.78
3.66
3.55
3.41
3.25
29
SHC
4.31
4.20
4.08
3.97
3.83
3.67
31
SHC
4.73
4.62
4.50
4.38
4.25
4.09
TC
6.34
6.06
5.79
5.51
5.18
4.77
CM
1.40
1.52
1.62
1.74
1.95
2.15
23
SHC
2.60
2.48
2.36
2.25
2.12
1.96
21
25
SHC
3.01
2.90
2.78
2.67
2.54
2.38
27
SHC
3.43
3.32
3.20
3.09
2.96
2.80
29
SHC
3.85
3.74
3.62
3.51
3.38
3.22
31
SHC
4.27
4.16
4.04
3.93
3.80
3.63
TC
6.73
6.44
6.13
5.79
5.42
5.04
CM
1.43
1.56
1.67
1.79
2.00
2.21
23
25
SHC
2.53
2.41
2.30
2.17
2.03
1.90
27
SHC
2.95
2.83
2.72
2.59
2.45
2.32
29
SHC
3.37
3.25
3.14
3.01
2.87
2.74
31
SHC
3.79
3.67
3.55
3.43
3.29
3.15
TC :
Total Cooling Capacity (kW)
SHC : Sensible Heat Capacity (kW)
CM :
Compressor Input (kW)
Rating conditions (#Mark) are
Outdoor Ambient Temp. 35°C D.B.
Indoor Unit Entering Air Temp. 27°C D.B. / 19°C W.B.
NOTE
A : SAP–K91GJA
B : SAP–K91GJA
Содержание SAP-CM1621GA
Страница 49: ......
Страница 50: ...SANYO Electric Co Ltd Osaka Japan SM700468 11 00 200 Printed in Japan ...