20
7. ELECTRICAL DATA
7-1. Electrical Characteristics
Indoor Unit
Outdoor Unit
Complete Unit
Fan Motor
Fan Motor
Compressor
Performance at
230V Single phase 50Hz
Rating Conditions
Running Amps.
A
0.36
0.49
5.65
6.5
Power Input
kW
0.074
0.112
1.264
1.45
Full Load Conditions Running Amps.
A
0.36
0.49
6.85
7.7
Power Input
kW
0.074
0.112
1.534
1.72
Rating Conditions
: Indoor Air Temperature 27°C D.B. / 19°C W.B.
Outdoor Air Temperature 35°C D.B.
Full Load Conditions : Indoor Air Temperature 32°C D.B. / 23°C W.B.
Outdoor Air Temperature 43°C D.B.
Indoor Unit
SAP – K91GA (
✕
2)
Outdoor Unit
SAP – CM1621GA
Indoor Unit
Outdoor Unit
Complete Unit
Fan Motor
Fan Motor
Compressor
Performance at
230V Single phase 50Hz
Rating Conditions
Running Amps.
A
0.18
0.49
2.83
3.5
Power Input
kW
0.037
0.112
0.631
0.78
Full Load Conditions Running Amps.
A
0.18
0.49
3.63
4.3
Power Input
kW
0.037
0.112
0.811
0.96
Rating Conditions
: Indoor Air Temperature 27°C D.B. / 19°C W.B.
Outdoor Air Temperature 35°C D.B.
Full Load Conditions : Indoor Air Temperature 32°C D.B. / 23°C W.B.
Outdoor Air Temperature 43°C D.B.
Indoor Unit
SAP – K91GJA (
✕
1)
Outdoor Unit
SAP – CM1621GA