REMOTE
1
CONTROL UNIT
852.6.4189.212.01.1
INSTALLATION INSTRUCTIONS
Ð Split system air conditioner Ð
DECLARATION OF CONFORMITY
This product is marked as it satisfies Directives:
– Low voltage no. 73/23 EEC and 93/68 EEC.
– Electromagnetic compatibility no. 89/336 ECC, 92/31 EEC
and 93/68 EEC.
This declaration will become void in case of misuse and/or non
observance though partial of manufacturer's installation and/or
operating instructions.
COOLING ONLY MODELS
OPERATING LIMITS
L
Maximum conditions
Outdoor temperature :
52°C D.B.*
Room temperature
:
35°C D.B. / 22.5°C W.B.
L
Minimum conditions
Outdoor temperature :
19°C D.B.**
Room temperature
:
19°C D.B. / 14°C W.B.
L
Model name CXXXL
* : 50°C D.B.
** : –15°C D.B.
HEAT PUMP MODELS
OPERATING LIMITS
L
Cooling Maximum conditions
Outdoor temperature :
46°C D.B.
Room temperature
:
35°C D.B. / 22°C W.B.
L
Cooling Minimum conditions
Outdoor temperature :
19°C D.B.
Room temperature
:
19°C D.B. / 14°C W.B.
L
Heating Maximum conditions
Outdoor temperature :
24°C D.B. / 18°C W.B.
Room temperature
:
27°C D.B.
L
Heating Minimum conditions
Outdoor temperature :
–8°C D.B. / –9°C W.B.
ACCESSORIES SUPPLIED WITH THE UNIT
PARTS
FIGURE
Q.TY
PARTS
FIGURE
Q.TY
RAWL PLUG
7
PLASTIC
1
COVER
HEX
1
WRENCH
TAPPING
6
SCREW
REMOTE CONTROL
1
UNIT SCREW
AAA ALKALINE
2
BATTERY
DRAIN
1
ELBOW
*
Power Supply:
The last digit(s) of the model number indicates the required
power supply to the unit.
5:
220 - 240 V ~ 50 Hz /
38:
380-400 V - 3N ~ 50 Hz
Last digit(s) of the model number
1. Standard screwdriver
2. Phillips head screwdriver
3. Knife or wire stripper
4. Tape measure
5. Level
6. Sabre saw or key hole saw
7. Hacksaw
8. Core bits ø 5
1
9. Hammer
10. Drill
11. Tube cutter
12. Tube flaring tool
13. Torque wrench
14. Adjustable wrench
15. Reamer (for reburring)
*
Available only for heat pump models.
Model Combinations
Combine indoor and outdoor units only as listed below.
COOLING ONLY MODELS R22
Indoor Units
Outdoor Units
SAP-KR165QS5
SAP-C165Q5
SAP-KR185QS5
SAP-C185Q5
SAP-C185QL5
SAP-C185Q38
SAP-C185QL38
SAP-KR225QS5
SAP-C225Q5
SAP-C225Q38
HEAT PUMP MODELS R22
Indoor Units
Outdoor Units
SAP-KR186QHS5
SAP-C186QH5
SAP-C186QH5N
SAP-C186QH38
SAP-C186QH38N
SAP-KR226QHS5
SAP-C226QH5
SAP-C226QH38
COOLING ONLY MODELS R407C
Indoor Units
Outdoor Units
SAP-KR165QS5
SAP-CR165G5
SAP-KR185QS5
SAP-CR185G5
SAP-CR185GL5
SAP-CR185G38
SAP-CR185GL38
SAP-KR225QS5
SAP-CR225G5
SAP-CR225G38
HEAT PUMP MODELS R407C
Indoor Units
Outdoor Units
SAP-KR186QHS5
SAP-CR186GH5N
SAP-CR186GH38N
SAP-KR226QHS5
SAP-CR226GH5
SAP-CR226GH38
EG
I
F
D
E
P
GR
©SANYO 2000
R407C MODELS: for the other installation works of CR models refer to
the “Installation Instructions” (green pages) on the top of the outdoor unit.
COOLING ONLY MODELS (R407C)
OPERATING LIMITS
L
Maximum conditions
Outdoor temperature :
43°C D.B.
Room temperature
:
32°C D.B. / 23°C W.B.
L
Minimum conditions
Outdoor temperature :
19°C D.B.*
Room temperature
:
19°C D.B. / 14°C W.B.
L
Model name CXXXL
* : –15°C D.B.
Tools required for installation (not supplied)