I - 85
SM830063
1
ECO MULTI SYSTEM Unit Specifications
MODEL No.
Indoor Unit
SPW-UR363GH56
POWER SOURCE
220 - 230 - 240 V / 1 phase / 50Hz
PERFORMANCE
Cooling
Heating
Capacity
kW
10.6
11.4
BTU / h
36,000
39,000
Air circulation (Hi / Me / Lo)
m
3
/ h
1,920 / 1,440 / 1,200
External static pressure (High)
mmAq (Pa)
7 (69): at shipment, 12 (118): using the booster cable
Moisture removal (High)
Liters / h
3.8
—
ELECTRICAL RATINGS
Voltage rating
V
220 - 230 - 240
Available voltage range
V
198 – 264
Running amperes
A
1.43 -
1.47 -
1.54
1.43 -
1.47 - 1.54
Power input
W
290 -
310 -
340
290 -
310 -
340
Power factor
%
92 -
92 -
92
92 -
92 -
92
Fan motor locked rotor amperes
A
2 - 2 - 2
FEATURES
Controls
Microprocessor
Timer
ON / OFF Timer (Max. 72 hr)
Fan speeds
3 and Automatic control
Air filter
Field supply
Refrigerant control
Electronic expansion valve
Operation sound
(Hi / Me / Lo)
dB-A
42 / 36 / 30
using the booster cable (Hi / Me / Lo)
dB-A
46 / 42 / 38
Refrigerant tubing connections
Flare type
Refrigerant tube
Narrow tube mm (in)
9.52 (3 / 8)
diameter
Wide tube
mm (in)
19.05 (3 / 4)
Drain connection
25 A, OD32 mm
Drain pump
Max. head 25 cm above drain connection
Remote Controller
Optional (RCS-SH80TG)
Refrigerant tubing kit / Accessories
Optional / Booster cable
DIMENSIONS & WEIGHT
Unit dimensions
Package dimensions
Dimensions
Height
mm (in)
310 ( 12 - 1 / 4)
380 ( 15
-
)
Width
mm (in)
1,480 ( 58 - 1 / 4)
1,679 ( 66 - 3 / 32)
Depth
mm (in)
665 ( 26 - 1 / 4)
866 ( 34 - 1 / 4)
Net weight
kg (lb)
64 (
141
)
Shipping weight
kg (lb)
71 (
157
)
Shipping volume
m
3
(cu. ft)
0.55 ( 19.5
)
Unit specifications (E)
7. Concealed Duct Type
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Rated conditions
Cooling: Indoor air temperature 27
°
C DB / 19
°
C WB, Outdoor air temperature 35
°
C DB
Heating: Indoor air temperature 20
°
C DB
, Outdoor air temperature 7
°
C DB / 6
°
C WB