ECO MULTI SYSTEM Unit Spesifications
SM830063
I - 6
1
Unit specifications (D)
MODEL No.
Outdoor Unit
SPW – CR483GV8
POWER SOURCE
380 - 400 - 415 V / 3 N / 50Hz
PERFORMANCE
Cooling
Capacity
kW
14
BTU / h
47,800
Air circulation (Hi)
m
3
/min(cu. ft/min)
84 (2,790)
ELECTRICAL RATINGS
Voltage rating
V
380
400
415
Available voltage range
V
342 - 456
Running amperes
A
9.5
9.5
9.4
Max. running amperes*
A
10.4
10.2
10.1
Power input
kW
5.54
5.61
5.65
Max. power input*
kW
6.03
6.05
6.05
Power factor
%
89
85
84
C.O.P
W/W
2.53
2.5
2.48
Compressor locked rotor amperes
A
62
65
67
FEATURES
Controls
Microprocessor
Defrost control
Reverse cycle, microprocessor control
Service function
Sensor temp. recall function
Past service warnings recall function
Refrigerant amount at shipment
kg
R407C - 3.6
Refrigerant control
Electronic expansion valve
Operation sound (Hi)
dB-A
55
External finish
Galvanized steel plate with powder paint
Color (Approximate value)
Munsell 5Y8.4 / 0.5, RAL 9002-GL
REFRIGERANT TUBING
Limit of tubing length
m(ft.)
70 (230)
Limit of elevation difference
m(ft.)
Outdoor unit is higher than indoor unit : 40 (131)
between the two units
Outdoor unit is lower than indoor unit : 30 (98)
Refrigerant tube
Narrow tube mm (in)
9.52 ( 3 / 8 )
outer diameter
Wide tube
mm (in)
19.05 ( 3 / 4 )
Refrigerant tubing kit / joint kit
Optional
DIMENSIONS & WEIGHT
Unit dimensions
Package dimensions
Unit dimensions
Height
mm(in)
1,235 (48 - 20 / 32)
1,326 (52 - 7 / 32)
Width
mm(in)
940 (37
)
1,016 (40
)
Depth
mm(in)
340 (13 - 12 / 32)
416 (16 - 12 / 32)
Net weight
kg(lb)
118 (
260
)
Shipping weight
kg(lb)
125 (
276
)
Shipping volume
m
3
(Cu. ft.)
0.56 (
19.8 )
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Rated conditions
Cooling: Indoor air temperature 27
°
C DB / 19.0
°
C WB
, Outdoor air temperature 35
°
C DB
* Full load conditions at Indoor / outdoor capacity ratio 130 %
Cooling: Indoor air temperature 32
°
C DB / 22.5
°
C WB , Outdoor air temperature 43
°
C DB / 25.5
°
C WB