ECO MULTI SYSTEM Unit Specifications
SM830063
I - 72
1
6. Ceiling Mounted Type
MODEL No.
Indoor Unit
SPW-TR483GH56
POWER SOURCE
220 - 230 - 240 V / 1 phase / 50Hz
PERFORMANCE
Cooling
Heating
Capacity
kW
14.0
16.0
BTU / h
47,800
54,600
Air circulation (Hi / Me / Lo)
m
3
/ h
1,920 / 1,680 / 1,320
Moisture removal (High)
Liters / h
7.0
—
ELECTRICAL RATINGS
Voltage rating
V
220 - 230 - 240
Available voltage range
V
198 – 264
Running amperes
A
0.95 -
0.96 -
0.98
0.86 -
0.88 - 0.90
Power input
W
200 -
210 -
220
180 -
190 -
200
Power factor
%
96 -
95 -
94
95 -
94 -
93
Fan motor locked rotor amperes
A
2 - 2 - 2
FEATURES
Controls
Microprocessor
Timer
ON / OFF Timer (Max. 72 hr)
Fan speeds
(Indoor unit)
3 and Automatic control
Air filter
Washable, easy access, long life (2,500 hr)
Refrigerant control
Electronic expansion valve
Operation sound
(Hi / Me / Lo)
dB-A
44 / 41 / 37
Refrigerant tubing connections
Flare type
Refrigerant tube
Narrow tube mm (in)
9.52 (3 / 8)
diameter
Wide tube
mm (in)
19.05 (3 / 4)
Drain connection
20 A, OD26 mm
Remote Controller
Optional (RCS-SH80TG)
Refrigerant tubing kit / Accessories
Optional / —
Color (Approximate value)
Munsell 10Y9.3 / 0.4, RAL 9010-GL
DIMENSIONS & WEIGHT
Unit dimensions
Package dimensions
Dimensions
Height
mm (in)
240 ( 9 - 7 /16)
317 ( 12 - 15 /32)
Width
mm (in)
1,575 ( 62 )
1,678 ( 66 - 1 /16)
Depth
mm (in)
670 ( 26 - 3 / 8)
789 ( 31 - 1 /16)
Net weight
kg (lb)
38 (
84
)
Shipping weight
kg (lb)
44 (
97
)
Shipping volume
m
3
(cu. ft)
0.42 ( 14.8
)
Unit specifications (D)
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Rated conditions
Cooling: Indoor air temperature 27
°
C DB / 19
°
C WB, Outdoor air temperature 35
°
C DB
Heating: Indoor air temperature 20
°
C DB
, Outdoor air temperature 7
°
C DB / 6
°
C WB