I - 82
SM830063
ECO MULTI SYSTEM Unit Specifications
1
Unit specifications (B)
MODEL No.
Indoor Unit
SPW-UR123GH56
POWER SOURCE
220 - 230 - 240 V / 1 phase / 50Hz
PERFORMANCE
Cooling
Heating
Capacity
kW
3.6
4.2
BTU / h
12,000
14,000
Air circulation (Hi / Me / Lo)
m
3
/ h
600 / 490 / 400
External static pressure (High)
mmAq (Pa)
5 (49): at shipment, 10 (98): using the booster cable
Moisture removal (High)
Liters / h
1.8
—
ELECTRICAL RATINGS
Voltage rating
V
220 - 230 - 240
Available voltage range
V
198 – 264
Running amperes
A
0.56 -
0.58 -
0.60
0.56 -
0.58 - 0.60
Power input
W
120 -
130 -
140
120 -
130 -
140
Power factor
%
97 -
97 -
97
97 -
97 -
97
Fan motor locked rotor amperes
A
1 - 1 - 1
FEATURES
Controls
Microprocessor
Timer
ON / OFF Timer (Max. 72 hr)
Fan speeds
3 and Automatic control
Air filter
Field supply
Refrigerant control
Electronic expansion valve
Operation sound
(Hi / Me / Lo)
dB-A
32 / 28 / 23
using the booster cable (Hi / Me / Lo)
dB-A
37 / 34 / 31
Refrigerant tubing connections
Flare type
Refrigerant tube
Narrow tube mm (in)
9.52 (3 / 8)
diameter
Wide tube
mm (in)
12.7 (1 / 2)
Drain connection
25 A, OD32 mm
Drain pump
Max. head 25 cm above drain connection
Remote Controller
Optional (RCS-SH80TG)
Refrigerant tubing kit / Accessories
Optional / Booster cable
DIMENSIONS & WEIGHT
Unit dimensions
Package dimensions
Dimensions
Height
mm (in)
310 ( 12 - 1 / 4)
380 (15
-
)
Width
mm (in)
750 ( 29 -17 / 32)
949 ( 37 - 3 / 8)
Depth
mm (in)
665 ( 26 - 1 / 4)
866 ( 34 - 1 / 16)
Net weight
kg (lb)
31 (
68
)
Shipping weight
kg (lb)
37 (
82
)
Shipping volume
m
3
(cu. ft)
0.312 ( 11.0
)
7. Concealed Duct Type
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Rated conditions
Cooling: Indoor air temperature 27
°
C DB / 19
°
C WB, Outdoor air temperature 35
°
C DB
Heating: Indoor air temperature 20
°
C DB
, Outdoor air temperature 7
°
C DB / 6
°
C WB