SM830063
I - 143
1
ECO MULTI SYSTEM Unit Specifications
11-3. Other component specifications
11. 1-Way Air Discharge Semi-concealed-Slim Type (SL Type)
MODEL NO.
Indoor Unit
SPW-SLR93 ~ 253GH56
Power Transformer
ATR-II215TB
Rated
Primary
V, Hz
AC 230 V, 50 Hz
Secondary
10.2 V, 1.4 A
14 V, 0.5 A
Coil resistance
Ω
WHT - WHT : 112
BRN - BRN :
0.5
RED - RED :
2.3
Thermal cut off temperature
˚C
150
Thermistor (Coil sensor)
PB3M-41E-S4 , PBC-41E-S25 , PBC-41E-S36
Resistance
K
Ω
-10 ˚C : 23.7
±
5 %
,
20 ˚C : 6.5
±
5 %
-5 ˚C : 18.8
±
5 %
,
30 ˚C : 4.4
±
5 %
0 ˚C : 15.0
±
5 %
,
40 ˚C : 3.1
±
5 %
5 ˚C : 12.1
±
5 %
,
45 ˚C : 2.6
±
5 %
10 ˚C : 9.7
±
5 %
Thermistor (Room or coil sensor)
KTEC-35-S6
Resistance
K
Ω
0 ˚C : 16.5
±
5 %
,
40 ˚C : 2.7
±
5 %
5 ˚C : 12.8
±
5 %
,
45 ˚C : 2.2
±
5 %
10 ˚C : 10.0
±
5 %
,
50 ˚C : 1.8
±
5 %
20 ˚C :
6.3
±
5 %
,
55 ˚C : 1.5
±
5 %
30 ˚C :
4.0
±
5 %
Electronic expansion valve
Valve body
IKV-24D12
Coil
DKV-MOZS550E0
Drain pump
WP20SL-19
Rated
AC 230 V, 14.7 W
Float switch
FS-0218-103
Rated (Contact rated)
DC 12 V, 25 W