110
11-
8
-5. Indicating (marking) the indoor and outdoor unit combination number
Indicate (mark) the number after automatic address setting is completed.
(1) So that the combination of each indoor unit can be easily checked when multiple units are installed, ensure that the
indoor and outdoor unit numbers correspond to the system address number on the outdoor unit control PCB, and
use a magic marker or similar means which cannot be easily erased to indicate the numbers in an easily visible
location on the indoor units (near the indoor unit nameplates).
Example: (Outdoor) 1 - (Indoor) 1-1...(Outdoor) 2 - (Indoor) 2-2...
(2) These numbers will be needed for maintenance. Be sure to indicate them.
* Use the remote controller to check the addresses of the indoor units. Press and hold the
button and
button for 4 seconds or longer (simple settings mode). Then press the
button and select the indoor
address. (Each time the button is pressed, the address changes as follows: 1-1, 2-1, ....) The indoor unit fan
operates only at the selected indoor unit. Confirm that correct fan is operating, and indicate address on the
indoor unit.
Press the
button again to return to the normal remote controller mode.
For details, refer to the separate handbook.
11-
8
-6. Main-sub remote controller control
Control using 2 remote controller switches
Main-sub remote controller control refers to the use of 2 remote controllers to control 1 indoor unit.
(A maximum of 2 remote controllers can be connected.)
Connecting 2 remote controllers to
control 1 indoor unit
1 2
1 2
1 2
U1U2
1 2
Remote co
n
troller wiri
ng
Optio
n
al
Optio
n
al
Remote co
n
troller
s
witch (
su
b)
Remote co
n
troller
s
witch (mai
n
)
I
n
door
un
it
O
u
tdoor
un
it
Gro
un
d
G
G
Gro
un
d
for remote
co
n
troller wiri
ng
Termi
n
al plate
(Setting procedure)
(1) Set 1 of the 2 connected remote controllers as the main
remote controller.
(2) On the other remote controller (sub remote controller),
change the remote controller address connector on the
reverse side of the remote controller switch PCB from the
Main position to the Sub position.
The remote controller will now function as the sub remote
controller.
Fig. 11-
8
Remote co
n
troller
Remote co
n
troller
addre
ss
co
nn
ector
RCU. ADR
Mai
n
Su
b
RCU check