Santa Fe Impact Installation & Operation Instructions

www.Santa-Fe-Products.com | 1-800-533-7533

Service - Troubleshooting

 CAUTION!

TROUBLESHOOTING SHOULD BE PERFORMED BY A QUALIFIED HVAC TECHNICIAN.

  Symptom 

Possible Reason 

Troubleshooting Procedure

 

Troubleshooting Procedure for Performance  

Related Issues
This method of diagnosis is used to function 
check the internal components in the dehumidifier. 
This is to be used when a performance issue is 
suspected.
1.  Set the humidity controller all the way to the 

most humid setting or off position – Did the 
unit shut off?

2.  If yes, turn the fan setting to the ON position – 

does the fan start?

3.  If fan starts, leave in the fan ON position and 

set the humidity all the way to driest setting. 
May have to wait 5 minutes for the compressor 
to start.

4.  Listen for a distinct buzzing/humming sound 

of a compressor starting up – do you hear this 
noise?

5.  If compressor is running and continues to run, 

after about 15 minutes you should feel a slight 
increase in air temperature being discharged 
out of the discharge air side of the unit.

6.  If so, depending on your environmental  

conditions (temp/Rh%), you should see some 
water production out of the hose within  
30 minutes or so. (

Note: If the room  

temperature is 55 degrees or below and/or  

in area of low relative humidity, the  

dehumidifier will produce little to no water.)

7.  Collecting the water removed in a 24 hour period 

will give a measurement of performance. 

 WARNING!

 

ELECTRICAL SHOCK HAZARD:

  

ELECTRICAL POWER MUST BE PRESENT 

TO PERFORM SOME TESTS. THESE TESTS 

SHOULD BE PERFORMED BY A QUALIFIED 

SERVICE PERSON.

Fan is not running. 
Dehumidification  
or fan is being 
called for.

1.  Loose connection in  

fan circuit.

2.  Obstruction prevents 

fan impeller rotation.

3. Defective fan.
4. Defective fan relay.

Low dehumidification 
capacity (evaporator 
is frosted  
continuously).  
Dehumidification is 
being called for.

1.  Defrost thermostat loose 

or defective.

2. Low refrigerant charge.
3.  Dirty air filter(s) or air flow 

restricted.

4.  Excessively restrictive 

ducting connected to unit.

Dehumidifier  
removes some  
water, but not as 
much as expected. 

1.  Air temperature and/or  

humidity have dropped. 

2.  Humidity meter and or 

thermometer used are  
out of calibration.

3.  Unit has entered defrost 

cycle. 

4.  Dirty air filter(s) or air flow 

is restriced. 

5.  Defective defrost  

thermostat. 

6. Low refrigerant charge. 
7.  Air leak such as loose 

cover or ducting leaks. 

8. Defective compressor. 
9. Restrictive ducting. 

Содержание 4032230

Страница 1: ...ies up to 2 500 square feet and is the ideal unit for meeting aggressive energy use targets The Santa Fe Impact is engineered for extremely quiet operation and is optimized for low heat load P N 40322...

Страница 2: ...Precautions 5 Location Considerations 5 Installing Leveling Feet 5 Ducting to Finished Areas Optional 6 Attaching Duct Collars 6 Recommended Installations 7 Drain Installation 8 Operation 9 Humidity C...

Страница 3: ...shelf or table Before leaving the unit unattended ensure children do not have access to the equipment Do not allow children to play with or near the unit or in its air flow The unit is designed to be...

Страница 4: ...nts Day 85 Pints Day Efficiency 8 8 Pints kWh 7 8 Pints kWh Energy Factor 4 2 L kWh 3 7 L kWh Air Filter MERV 11 Standard Pleat Size 16 x 20 x 2 Power Cord 9 115 VAC Ground Drain Connection 3 4 Thread...

Страница 5: ...a 15 Amp circuit capacity The unit is designed to operate while level If the unit is placed on an unlevel surface refer to section below Installing Leveling Feet Failure to level the unit may result i...

Страница 6: ...r duct collar and a front panel are attached to the unit Supply Air Outlet Two 10 diameter duct collars attach to the outlets on each side of the unit CAUTION BOTH EXHAUST OUTLETS MUST BE LEFT OPEN OR...

Страница 7: ...m being placed under a negative pressure and also allow the dehumidifier to focus on keeping the unfinished area dry as well The onboard dehumidistat control can be used on the unit for this applicati...

Страница 8: ...Optional Drain Port Drain Trap Pretzel Loop Floor Bend PVC Trap PVC materials available from your local hardware store Standard Loop The Santa Fe Impact requires a drain trap Creating a drain trap all...

Страница 9: ...he humidity dial clockwise to the recommended NORMAL position and set fan control to FAN AUTO To turn the unit off turn the humidity dial counter clockwise to the OFF position and set fan control to F...

Страница 10: ...SE PREMATURE FILTER WEAR OR UNIT DAMAGE MERV 8 Filter Changing the Filter For greatest filtration and efficiency of the Santa Fe Impact it is recommended the air filter be replaced every three to six...

Страница 11: ...11 1 800 533 7533 www Santa Fe Products com Santa Fe Impact Installation Operation Instructions MERV Rating Chart Air Filtration http www mechreps com PDF Merv_Rating_Chart pdf...

Страница 12: ...Amp circuit capacity If used in an area that may become wet a GFCI protected circuit is recommended The unit should not be used in areas prone to flooding Consult local electrical codes for any furthe...

Страница 13: ...TA FE IMPACT WITH ITS HIGH PRESSURE REFRIGERANT SYSTEM AND HIGH VOLTAGE CIRCUITRY PRESENTS A HEALTH HAZARD WHICH COULD RESULT IN DEATH SERIOUS BODILY INJURY AND OR PROPERTY DAMAGE ONLY QUALIFIED SERVI...

Страница 14: ...s temp Rh you should see some water production out of the hose within 30 minutes or so Note If the room temperature is 55 degrees or below and or in area of low relative humidity the dehumidifier will...

Страница 15: ...oes not cover any costs related to changes to a Product or Component that may be required by any codes laws or regulations that may become effective after initial purchase of the Product by Customer C...

Страница 16: ...www Santa Fe Products com 1 800 533 7533...

Отзывы: