Santa Fe Impact Installation & Operation Instructions

Service

Replacement Parts

4026221 

Leveling Foot

4031085 

Condensor Coil

4031086-05  Evaporator Coil
4025741 

 Thermostat, Defrost Control

4029510 Filter/Drier
4035851 Compressor
4035871 

Compressor Overload

4032196 Impeller
4025560 

Fan Switch

4035087 Humidistat
4035235-02  Blower Capacitor, Run, 5MFD, 370V
4033032-03  Compressor Capacitor, Run, 35MFD, 370V

Refrigerant Charging 

If the refrigerant charge is lost due to service or a leak, 
a new charge must be accurately weighed in. If any of 
the old charge is left in the system, it must be recovered 
before weighing in the new charge. Refer to the  
unit nameplate for the correct charge weight and  
refrigerant type. 

Compressor/Capacitor Replacement 

This compressor is equipped with a two terminal 
external overload and a run capacitor, but no start 
capacitor or relay.

 WARNING!

SERVICING THE SANTA FE IMPACT, WITH ITS HIGH PRESSURE REFRIGERANT SYSTEM AND HIGH VOLTAGE 

CIRCUITRY PRESENTS A HEALTH HAZARD WHICH COULD RESULT IN DEATH, SERIOUS BODILY INJURY, AND/OR 

PROPERTY DAMAGE. ONLY QUALIFIED SERVICE PEOPLE SHOULD SERVICE THIS UNIT.

Troubleshooting

 CAUTION!

TROUBLESHOOTING SHOULD BE PERFORMED BY 

A QUALIFIED HVAC TECHNICIAN.

  Symptom 

Possible Reason

Neither fan nor 
compressor  
running.  
Dehumidification  
is being called for.

Compressor is  
not running.  
Dehumidification  
is being called for. 
Fan is running.

1.  Defective compressor 

run capacitor.

2.  Loose connection in 

compressor circuit.

3.  Defective compressor 

overload.

4.  Defective compressor.
5.  Defrost thermostat open.

Compressor 
cycles on and off. 
Dehumidification is 
being called for.

1.  Low ambient  

temperature and/or  
humidity causing unit  
to cycle through  
defrost mode.

2.  Defective compressor 

overload.

3.  Defective compressor.
4.  Defrost thermostat  

defective.

5.  Dirty air filter(s) or air 

flow restricted.

6. Defective fan or relay.

1.  Dehumidifier unplugged 

 or no power to outlet.

2.  Humidity control set  

too high.

3.  Loose connection in  

internal or control wiring.

4.  Defective compressor 

relay.

Содержание 4032230

Страница 1: ...ies up to 2 500 square feet and is the ideal unit for meeting aggressive energy use targets The Santa Fe Impact is engineered for extremely quiet operation and is optimized for low heat load P N 40322...

Страница 2: ...Precautions 5 Location Considerations 5 Installing Leveling Feet 5 Ducting to Finished Areas Optional 6 Attaching Duct Collars 6 Recommended Installations 7 Drain Installation 8 Operation 9 Humidity C...

Страница 3: ...shelf or table Before leaving the unit unattended ensure children do not have access to the equipment Do not allow children to play with or near the unit or in its air flow The unit is designed to be...

Страница 4: ...nts Day 85 Pints Day Efficiency 8 8 Pints kWh 7 8 Pints kWh Energy Factor 4 2 L kWh 3 7 L kWh Air Filter MERV 11 Standard Pleat Size 16 x 20 x 2 Power Cord 9 115 VAC Ground Drain Connection 3 4 Thread...

Страница 5: ...a 15 Amp circuit capacity The unit is designed to operate while level If the unit is placed on an unlevel surface refer to section below Installing Leveling Feet Failure to level the unit may result i...

Страница 6: ...r duct collar and a front panel are attached to the unit Supply Air Outlet Two 10 diameter duct collars attach to the outlets on each side of the unit CAUTION BOTH EXHAUST OUTLETS MUST BE LEFT OPEN OR...

Страница 7: ...m being placed under a negative pressure and also allow the dehumidifier to focus on keeping the unfinished area dry as well The onboard dehumidistat control can be used on the unit for this applicati...

Страница 8: ...Optional Drain Port Drain Trap Pretzel Loop Floor Bend PVC Trap PVC materials available from your local hardware store Standard Loop The Santa Fe Impact requires a drain trap Creating a drain trap all...

Страница 9: ...he humidity dial clockwise to the recommended NORMAL position and set fan control to FAN AUTO To turn the unit off turn the humidity dial counter clockwise to the OFF position and set fan control to F...

Страница 10: ...SE PREMATURE FILTER WEAR OR UNIT DAMAGE MERV 8 Filter Changing the Filter For greatest filtration and efficiency of the Santa Fe Impact it is recommended the air filter be replaced every three to six...

Страница 11: ...11 1 800 533 7533 www Santa Fe Products com Santa Fe Impact Installation Operation Instructions MERV Rating Chart Air Filtration http www mechreps com PDF Merv_Rating_Chart pdf...

Страница 12: ...Amp circuit capacity If used in an area that may become wet a GFCI protected circuit is recommended The unit should not be used in areas prone to flooding Consult local electrical codes for any furthe...

Страница 13: ...TA FE IMPACT WITH ITS HIGH PRESSURE REFRIGERANT SYSTEM AND HIGH VOLTAGE CIRCUITRY PRESENTS A HEALTH HAZARD WHICH COULD RESULT IN DEATH SERIOUS BODILY INJURY AND OR PROPERTY DAMAGE ONLY QUALIFIED SERVI...

Страница 14: ...s temp Rh you should see some water production out of the hose within 30 minutes or so Note If the room temperature is 55 degrees or below and or in area of low relative humidity the dehumidifier will...

Страница 15: ...oes not cover any costs related to changes to a Product or Component that may be required by any codes laws or regulations that may become effective after initial purchase of the Product by Customer C...

Страница 16: ...www Santa Fe Products com 1 800 533 7533...

Отзывы: