8/36
(2)
Connection of the vibration sensor
Firmly connect one end of the input cable (P4 cord, accessory) of the vibration sensor to the
connector on the board and connect the other end of the same to the vibration sensor
(KS-3).
※
1. To connect the vibration sensor input cable, the operation panel has to be detached.
Confirm the power-OFF status, and then detach the operation panel.
Note that the operation panel is connected to the controller main body with a
connecting wire. When attaching/detaching the operation panel, carefully watch out for
the connecting wire to avoid disconnection or pinching.
※
2. Limit the total length of the cable between the controller and the feeder (vibration
sensor) to 4m.
To extend the cable, be sure to use the dedicated cable of our make.
In wiring each cable, detach the wiring from the power cable.
4) Overflow sensor connection
Connect the overflow sensor to the terminal of the overflow sensor input cable (P3 cord).
The connection enabled sensor can use the NPN open collector output or the PNP open
collector output.
Before connecting the sensor, change the jumper pin settings.
[For NPN]
[For PNP]
Jumper pin position:
Jumper pin position:
Sensor: Brown
Sensor: Black
Sensor: Blue
Internal circuit
Sensor: Brown
Sensor: Black
Sensor: Blue
Internal circuit
Red [24V terminal No. A0]
–
Sensor brown wire
Black [0V terminal No. A3]
–
Sensor blue wire
White [Signal terminal No. A6]
–
Sensor black wire
[Terminal connector signal name of P3 cord]