6002, 6002-14B, 6002-A, and 6002-14A offer precision to assure the health and safety to occupants with the tightest possible controls
on energy consumption. They are versatile, self-contained dual gas sensors that are network ready for either peer-to-peer (master slave)
operation or central control for a smooth integration into new or existing energy management systems.
Applications:
• Vehicle Emissions
• Combustible Gases
• Refrigerant Gas Leak Detection
• Industrial Health and Safety
Features:
• Stand-alone operation with 1 or 2 adjustable alarm relays, indicators and strobe
• BACnet Laboratory (BTL) listed Smart Sensor, up to 76,800 baud
• BACnet MS/TP RS485 interface
• CAN network interface for master-slave operation or central control
• Pre-calibrated plug-and-play sensor modules
• Impact resistant, water resistant enclosure.
Specifications
:
• Supply 24 vac 50/60 hz (17-28 vac) 0.21 amps, 5 va
• Relays (1 or 2) SPDT, 5 amp @ 125 vac, non-inductive
• 6002-A and 6002-14A have 1 Relay and accept 4-20mA or 2-10V signals from VFDs or ECMs for speed control.
• On delay: 0-999 seconds (16 minutes)
• Off delay: 0-999 seconds (16 minutes)
• Operating temperature -20
º
C to 50
º
C (-4
º
F to 122
º
F)
• For indoor use
• Flame resistant Polycarbonate ABS enclosure rated UL94 V0, 5VB, and 5VA
• Standards. Conforms to UL61010-1, CSA C22.2 61010-1-12, ANSI/ISA 61010-1, CSA C22.2 no. 205-12
• Pollution degree 2
• Installation category II
• Altitude 2000m
• Humidity max 90% rh. 90% to temperatures up to 31
º
C (88
º
F), decreasing linearity to 50% rh at 40
º
C (104
º
F)
User Interface:
• Back lit LCD display shows gas concentration, user settings, calibration controls
• Red LED alarm indicators, gas level 1 and 2
• High intensity white LED strobe on level 3
• Audible alarm, 85 db at 1 meter
• 4 pushbutton user keypad
• Password control for settings