seconds to stop.
T
indicates alarm 1 on due to high ambient temperature (setting 51). Useful for summer ventilation.
Default Settings
User settings are factory pre-loaded with default values to facilitate set up and can be changed at any time. Upgrading firmware will not
affect user settings.
Alarm thresholds should be set to suit local regulations. Default values for these are general guidelines only.
Changing Settings
Press
→
and
←
to move through the settings. If the keypad lock is on then enter the password first. The screen will display the setting number
0, 1, 2, etc. plus the short description (e.g. AL1 for Alarm 1 and the current setting.)
Press the
↑
or
↓
buttons to increase or decrease the setting.
To save, press
↑
and
←
buttons at the same time. The word “OK” will appear. If you do not see “OK” and the new value it is because the
buttons were not pressed simultaneously. Try again.
List of Settings Sensor A (upper socket) Settings
NO.
Name
Description
Range
Default
0
AL1
Alarm 1 threshold, activates relay 1
by sensor
1
A1Del
Alarm 1 Delay on (seconds)
0-999
30
2
A1Off
Alarm 1 Delay off (seconds)
0-999
20
3
AL2
Alarm 2 threshold, activates relay 2
by sensor
4
A2Del
Alarm 2 Delay on (seconds)
0-999
30
5
A2Off
Alarm 2 Delay off (seconds)
0-999
20
6
AL3
Alarm 3 threshold, sounder and strobe
by sensor
7
A3Del
Alarm 3 Delay on (seconds)
0-999
180
8
A3Off
Alarm 3 Delay off (seconds)
0-999
20
9
A1Tx
Alarm 1 transmit message, CAN network
0-255
1
10
A1Tx
Alarm 1 transmit message, CAN network
0-255
11
A1Tx
Alarm 1 transmit message, CAN network
0-255
12
A2Tx
Alarm 2 transmit message, CAN network
0-255
2
13
A2Tx
Alarm 2 transmit message, CAN network
0-255
14
A2Tx
Alarm 2 transmit message, CAN network
0-255
15
A3Tx
Alarm 3 transmit message, CAN network
0-255
3
16
A3Tx
Alarm 3 transmit message, CAN network
0-255
17
A3Tx
Alarm 3 transmit message, CAN network
0-255
List of Settings Sensor B (lower socket) Settings
NO.
Name
Description
Range
Default
18
AL1-B
Alarm 1 threshold, activates relay 1
by sensor
19
A1Del
Alarm 1 Delay on (seconds)
0-999
30
20
A1Off
Alarm 1 Delay off (seconds)
0-999
20
21
AL2-B
Alarm 2 threshold, activates relay 2
by sensor
22
A2Del
Alarm 2 Delay on (seconds)
0-999
30
23
A2Off
Alarm 2 Delay off (seconds)
0-999
20
24
AL3-B
Alarm 3 threshold, sounder and strobe
by sensor
25
A3Del
Alarm 3 Delay on (seconds)
0-999
180
26
A3Off
Alarm 3 Delay off (seconds)
0-999
20
27
A1x,A1Tx Alarm 1 transmit message, CAN network
0-255
1