background image

seconds to stop.

T

 indicates alarm 1 on due to high ambient temperature (setting 51).  Useful for summer ventilation.

Default Settings

User settings are factory pre-loaded with default values to facilitate set up and can be changed at any time. Upgrading firmware will not 
affect user settings.

Alarm thresholds should be set to suit local regulations.  Default values for these are general guidelines only.

Changing Settings
Press 

 and 

 to move through the settings. If the keypad lock is on then enter the password first.  The screen will display the setting number 

0, 1, 2, etc. plus the short description (e.g. AL1 for Alarm 1 and the current setting.)

Press the 

↑ 

or

 ↓

 buttons to increase or decrease the setting.

To save, press 

↑ 

and 

← 

buttons at the same time.  The word “OK” will appear.  If you do not see “OK” and the new value it is because the 

buttons were not pressed simultaneously.  Try again.

List of Settings Sensor A (upper socket) Settings

 

NO.

Name

Description

Range

Default

0

AL1

Alarm 1 threshold, activates relay 1

by sensor

1

A1Del

Alarm 1 Delay on (seconds)

0-999

30

2

A1Off

Alarm 1 Delay off (seconds)

0-999

20

3

AL2

Alarm 2 threshold, activates relay 2

by sensor

4

A2Del

Alarm 2 Delay on (seconds)

0-999

30

5

A2Off

Alarm 2 Delay off (seconds)

0-999

20

6

AL3

Alarm 3 threshold, sounder and strobe

by sensor

7

A3Del

Alarm 3 Delay on (seconds)

0-999

180

8

A3Off

Alarm 3 Delay off (seconds)

0-999

20

9

A1Tx

Alarm 1 transmit message, CAN network

0-255

1

10

A1Tx

Alarm 1 transmit message, CAN network

0-255

11

A1Tx

Alarm 1 transmit message, CAN network

0-255

12

A2Tx

Alarm 2 transmit message, CAN network

0-255

2

13

A2Tx

Alarm 2 transmit message, CAN network

0-255

14

A2Tx

Alarm 2 transmit message, CAN network

0-255

15

A3Tx

Alarm 3 transmit message, CAN network

0-255

3

16

A3Tx

Alarm 3 transmit message, CAN network

0-255

17

A3Tx

Alarm 3 transmit message, CAN network

0-255

List of Settings Sensor B (lower socket) Settings

NO.

Name

Description

Range

Default

18

AL1-B

Alarm 1 threshold, activates relay 1

by sensor

19

A1Del

Alarm 1 Delay on (seconds)

0-999

30

20

A1Off

Alarm 1 Delay off (seconds)

0-999

20

21

AL2-B

Alarm 2 threshold, activates relay 2

by sensor

22

A2Del

Alarm 2 Delay on (seconds)

0-999

30

23

A2Off

Alarm 2 Delay off (seconds)

0-999

20

24

AL3-B

Alarm 3 threshold, sounder and strobe

by sensor

25

A3Del

Alarm 3 Delay on (seconds)

0-999

180

26

A3Off

Alarm 3 Delay off (seconds)

0-999

20

27

A1x,A1Tx Alarm 1 transmit message, CAN network

0-255

1

Содержание 6002-A

Страница 1: ...022020 Gas Detectors READ AND SAVE THESE INSTRUCTIONS The purpose of this manual is to aid in the proper installation and operation of fans manufactured by Soler Palau USA These instructions are inten...

Страница 2: ...ct resistant water resistant enclosure Specifications Supply 24 vac 50 60 hz 17 28 vac 0 21 amps 5 va Relays 1 or 2 SPDT 5 amp 125 vac non inductive 6002 A and 6002 14A have 1 Relay and accept 4 20mA...

Страница 3: ...Wiring for Model 60xx A Wiring Model 60xx B...

Страница 4: ...configuration Make all chain connections at the sensors to avoid T connections 6 Move the end of line jumper the one above terminal 1 1 12 to the on position UP on the first sensor or controller on th...

Страница 5: ...d be installed at 50 of the ceiling height and above the vehicle height If the exhaust pipes of diesel vehicles are below the vehicles then the nitrogen dioxide detectors should be installed at 3 to 5...

Страница 6: ...2 threshold activates relay 2 by sensor 4 A2Del Alarm 2 Delay on seconds 0 999 30 5 A2Off Alarm 2 Delay off seconds 0 999 20 6 AL3 Alarm 3 threshold sounder and strobe by sensor 7 A3Del Alarm 3 Delay...

Страница 7: ...ing this option forces output low for testing 43 AnSB Adjustment for analog span output 20ma or 10V sensor B to tweak output for controller input errors Accessing this option forces output high for te...

Страница 8: ...start The timer will clear if the gas rises above the alarm setting 8 When the Delay Off Timer times out the relay 1 will de energize the Alarm 1 LED will turn off and the Relay 1 Transmit message wi...

Страница 9: ...he relays usually level 1 This is a configuration for one ventilation zone Creating Zones or groups To control multiple zones on the same network set the transmit message on each sensor to different m...

Страница 10: ...span and the current gas reading 8 Inject bottled span gas into first sensor and wait until the gas reading stops going up The span gas should must be within the range of sensor s scale 9 Adjust the...

Страница 11: ...hen returned to our factory transportation prepaid Deterioration or wear by heat abrasive action chemicals improper installation or operation or lack of normal maintenance shall not constitute defects...

Страница 12: ...or consequential damages including but not limited to loss of profits or revenue loss of use of the equipment or any associated equipment cost of capital cost of substitute equipment facilities or se...

Отзывы: