Ventilation Controlled by BACnet Building Automation

Object Table

Type and Instance

Object Name

Object Property

Parameter

AV 0

gas reading 1

Present value (R)

Gas reading local sensor A

AV 1

gas reading 2

Present value (R)

Gas reading local sensor B

AV 2

Ambient temperature

Present value (R)

Temperature in celsius

BI 0

Input 1

Present value (R)

Auxiliary input state 0/1

B0 0

Relay 1

Present value (R/W)

Relay 1 status on 0/1

B0 1

Relay 2 0r alarm 2

Present value (R/W)

Relay 2 or alarm 2 status 0/1

B0 2

Alarm 3

Present value (R/W)

Alarm 3 Indicator status 0/1

AV XYY

Gas reading XYY

X = sensor 1 (top) or 2 (bottom), YY = CAN 
Address

Present value (R)

Gas reading all sensors on CAN network

WARRANTY:

Soler & Palau USA warrants this controller equipment to be free from defects in material and workmanship for two (2) years from date of 
shipment and the sensor will have a one (1) year from date of shipment. Any units or parts which prove to be defective and are reported 
during the warranty period will be replaced at our option when returned to our factory, transportation prepaid. Deterioration or wear by 
heat, abrasive action, chemicals, improper installation or operation or lack of normal maintenance shall not constitute defects, and are not 
covered by warranty.

The motor is warranted by the motor manufacturer for one (1) year. If the motor becomes defective in the warranty period, it should be taken 
to the nearest authorized motor service station.  If this is not done, the motor manufacturer will not warrant the motor. Call the factory for 
instructions if authorized service station is not known.

Soler & Palau USA will not be responsible for any installation, removal or re-installation costs or any consequential damage resulting in 
failure to meet conditions of any warranty.

LIMITATION OF WARRANTY AND LIABILITY

This warranty does not apply to any such S&P product or parts which have failed as a result of faulty installation or abuse, or incorrect 
electrical connections or alterations, made by others, or use under abnormal operating conditions or misapplication of the products and 
parts.
Soler & Palau USA will not approve for payment any repairs made outside the factory without prior written consent of its Jacksonville, 
Florida office.

Содержание 6002-A

Страница 1: ...022020 Gas Detectors READ AND SAVE THESE INSTRUCTIONS The purpose of this manual is to aid in the proper installation and operation of fans manufactured by Soler Palau USA These instructions are inten...

Страница 2: ...ct resistant water resistant enclosure Specifications Supply 24 vac 50 60 hz 17 28 vac 0 21 amps 5 va Relays 1 or 2 SPDT 5 amp 125 vac non inductive 6002 A and 6002 14A have 1 Relay and accept 4 20mA...

Страница 3: ...Wiring for Model 60xx A Wiring Model 60xx B...

Страница 4: ...configuration Make all chain connections at the sensors to avoid T connections 6 Move the end of line jumper the one above terminal 1 1 12 to the on position UP on the first sensor or controller on th...

Страница 5: ...d be installed at 50 of the ceiling height and above the vehicle height If the exhaust pipes of diesel vehicles are below the vehicles then the nitrogen dioxide detectors should be installed at 3 to 5...

Страница 6: ...2 threshold activates relay 2 by sensor 4 A2Del Alarm 2 Delay on seconds 0 999 30 5 A2Off Alarm 2 Delay off seconds 0 999 20 6 AL3 Alarm 3 threshold sounder and strobe by sensor 7 A3Del Alarm 3 Delay...

Страница 7: ...ing this option forces output low for testing 43 AnSB Adjustment for analog span output 20ma or 10V sensor B to tweak output for controller input errors Accessing this option forces output high for te...

Страница 8: ...start The timer will clear if the gas rises above the alarm setting 8 When the Delay Off Timer times out the relay 1 will de energize the Alarm 1 LED will turn off and the Relay 1 Transmit message wi...

Страница 9: ...he relays usually level 1 This is a configuration for one ventilation zone Creating Zones or groups To control multiple zones on the same network set the transmit message on each sensor to different m...

Страница 10: ...span and the current gas reading 8 Inject bottled span gas into first sensor and wait until the gas reading stops going up The span gas should must be within the range of sensor s scale 9 Adjust the...

Страница 11: ...hen returned to our factory transportation prepaid Deterioration or wear by heat abrasive action chemicals improper installation or operation or lack of normal maintenance shall not constitute defects...

Страница 12: ...or consequential damages including but not limited to loss of profits or revenue loss of use of the equipment or any associated equipment cost of capital cost of substitute equipment facilities or se...

Отзывы: