S&P 6002-A Скачать руководство пользователя страница 8

65

AMinB

Analog drive. Minimum percent of scale for zero output. Sensor B

0-255

0

66

AMaxB

Analog drive. Maximum percent of scale for full scale output. Sensor B 0-100

100

67

ADRxB

Receive message code to control local 
Analog output B

0-255

0

68

Baud

Baud rate for CAN network
Maximum network wire length is 1500 feet at rate 0 and 3000 feet at 
rate 1.
Set Baud rate = 1 when used with model 5000 network

0-1

0

69

Man

Manual mode activates alarms 1, 1+2 or 1+2+3. See screen display 
section.

1-3

1

70

BDI

Bacnet device instance replace
default 60,000 + BMA (setting 47)
BACnet device instance replaces default 6

0-4,194,304

60000

Sequence of Operation

1.  Sensors are pre-loaded with options for normal operation and can be changed by the user at any time via the key pad.
2.  On power-up the display will show the software revision number and the Warm-Up Timer will count down (setting 52, default 1 

minute). Relays are inactive during this time. Press any button to cancel the warm-up period.

3.  The display will show the gas type and the current gas concentration. For dual-sensors the display will alternate between the two 

sensor modules and show the gas type and concentration of each. If the network display option is turned on (option 56) 
the display will show each sensor that is connected via the CAN network, its address, gas type and concentration. Detector will 
display for 3 seconds and then cycle to the next, lowest address to the highest and then start again.

4.  If the gas level rises above the Level One Set Point then the Delay- On Timer will start. The time setting range is from 1 to 999 seconds. 

If the gas level drops below level one the timer will reset and start over the next time it goes over.

5.  If the gas level stays above the Alarm 1 Level for the set time the relay 1 on-board will energize, and remain energized as long as 

the gas remains above the alarm setting. The bottom left corner of the display will indicate a 1 and the alann 1 LED will light up. In 
addition, the Alarm 1 Transmit Message (default is 1) will be sent to all detectors and controllers via the CAN network.

6.  All sensors or controllers on the CAN network with a Relay 1 Receive Message (setting 36) = 1 will energize their on-board relay 1, 

and display a 1 in the bottom left hand corner of their display.

7.  When the current gas concentration drops below the Alarm 1 set point, the Delay-Off time will start. The timer will clear if the gas rises 

above the alarm setting.

8.  When the Delay-Off Timer times out the relay 1 will de-energize, the Alarm 1 LED will turn off and the Relay 1 Transmit message will 

stop being sent, thereby de-energizing relays on other units.

9.  If the temperature exceeds the Hi Temperature Alarm, setting 51, relay 1 will activate, the Alarm 1 LED will turn on and the Alarm 1 

Transmit message will be sent via the CAN network to other sensors and controllers. When temperature drops one degree, the alarm 
1 will be turned off and the Alarm 1 Transmit message will stop being sent.

10.  If the gas level rises to the Alarm Level 2 setting, then the Level 2, Delay-On Timer will begin, and after timing-out the on-board relay 

2 will activate (for models 60xx-B only) the Alarm 2 LED will tum on, the Relay 2 Transmit message (default = 2) will be sent out on 
the CAN network activating remote units with that same Relay 2 Receive message (option 37).

11.  When the current gas concentration drops below the Alarm 2 setting, for longer than the Alarm 2 Off-Delay Setting the relay 2 will 

turn off, the Relay 2 LED will turn off, and the Relay 2 Transmit message will stop being sent on the CAN network.

12.  When the gas concentration rises above the Alarm Level 3 setting, for more than the Alarm 3 Delay-On timer the audible alarm will 

sound, the LED strobe flasher will start Qf (If enabled, setting 45), a 3 will appear in the bottom left corner of the display, and the 
Alarm 3 Transmit message (default 3) will be sent to other sensors or controllers. They can be silenced by pressing any button.

13.  When the gas concentration drops below the Alarm 3 set point for longer than the Alarm 3 Delay-Off setting then the audible alarm 

and strobe flasher will stop and the Alarm 3 Transmit message will stop being sent on the CAN network.

14.  On a sensor fault condition, the units will transmit the Fault Transmit Message, option 59, to other sensors or controllers.
15.  A Manual Over-ride mode is available to test relay functions and to activate ventilation. From the home screen press and hold the up 

arrow for 5 seconds. Press the up arrow to increase the timer by 5 minutes per click up to 60 minutes. The screen will display MAN 
5 and timer will energize relay 1 and send the Alarm 1 Transmit Message on the CAN network. After the time runs down the unit 
will return to automatic operation. To cancel, press the down arrow several times to reduce the timer to zero and return to normal 
operation. To activate alarm, Level 2 or 3 as well with this procedure, set option 69 to 2 or 3. 

Содержание 6002-A

Страница 1: ...022020 Gas Detectors READ AND SAVE THESE INSTRUCTIONS The purpose of this manual is to aid in the proper installation and operation of fans manufactured by Soler Palau USA These instructions are inten...

Страница 2: ...ct resistant water resistant enclosure Specifications Supply 24 vac 50 60 hz 17 28 vac 0 21 amps 5 va Relays 1 or 2 SPDT 5 amp 125 vac non inductive 6002 A and 6002 14A have 1 Relay and accept 4 20mA...

Страница 3: ...Wiring for Model 60xx A Wiring Model 60xx B...

Страница 4: ...configuration Make all chain connections at the sensors to avoid T connections 6 Move the end of line jumper the one above terminal 1 1 12 to the on position UP on the first sensor or controller on th...

Страница 5: ...d be installed at 50 of the ceiling height and above the vehicle height If the exhaust pipes of diesel vehicles are below the vehicles then the nitrogen dioxide detectors should be installed at 3 to 5...

Страница 6: ...2 threshold activates relay 2 by sensor 4 A2Del Alarm 2 Delay on seconds 0 999 30 5 A2Off Alarm 2 Delay off seconds 0 999 20 6 AL3 Alarm 3 threshold sounder and strobe by sensor 7 A3Del Alarm 3 Delay...

Страница 7: ...ing this option forces output low for testing 43 AnSB Adjustment for analog span output 20ma or 10V sensor B to tweak output for controller input errors Accessing this option forces output high for te...

Страница 8: ...start The timer will clear if the gas rises above the alarm setting 8 When the Delay Off Timer times out the relay 1 will de energize the Alarm 1 LED will turn off and the Relay 1 Transmit message wi...

Страница 9: ...he relays usually level 1 This is a configuration for one ventilation zone Creating Zones or groups To control multiple zones on the same network set the transmit message on each sensor to different m...

Страница 10: ...span and the current gas reading 8 Inject bottled span gas into first sensor and wait until the gas reading stops going up The span gas should must be within the range of sensor s scale 9 Adjust the...

Страница 11: ...hen returned to our factory transportation prepaid Deterioration or wear by heat abrasive action chemicals improper installation or operation or lack of normal maintenance shall not constitute defects...

Страница 12: ...or consequential damages including but not limited to loss of profits or revenue loss of use of the equipment or any associated equipment cost of capital cost of substitute equipment facilities or se...

Отзывы: