S&C Instruction Sheet 461-509
27
Configuring the Communication Gateway
Table 2. Import and Export Settings Configuration
Parameter Group
Attribute
Description
Data Type
Range of Value
<DNP3Masters>
<dnp3master/>
</DNP3Masters>
unsolicitedenabled
Boolean indicating whether the gateway will attempt to
send DNP3 unsolicited responses to the SCADA master .
See
Unsolicited Response on the
DNP3 Master Settings
screen .
Boolean
True or False
port
Gateway’s TCP or UDP listen port for receiving IP packets
from the SCADA master .
Integer
1024 … 49,151
ipaddress
SCADA master’s IP address . Currently ignored by the
gateway as it will accept traffic from any IP address . See
IPv4 Address on the
DNP3 Master Settings
screen .
IP address
(dotted
decimal)
Any valid IP
address
dnp3address
SCADA master’s DNP3 address. See
DNP3 Address
on
the DNP3 Master Settings screen.
Integer
1 … 65,519
<BinaryInputSetPoints>
<binaryinputsetpoint/>
</BinaryInputSetPoints>
statuspoint
See
Status Point on the
DNP3 Outstation Settings
screen .
Integer
0 … 147
codedescription
See
Code Description on the
DNP3 Outstation Settings
screen .
Integer
per 461-560
eventclass
See
Class on the
DNP3 Outstation Settings
screen . A
value of 0 corresponds to NO EVENT .
Integer
0,1,2,3
<AnalogInputSetPoints>
<analoginputsetpoint/>
</AnalogInputSetPoints>
statuspoint
See
Status Point on the
DNP3 Outstation Settings
screen .
Integer
0…20
codedescription
See
Code Description on the
DNP3 Outstation Settings
screen .
Integer
per 461-560
eventclass
See
Class on the
DNP3 Outstation Settings
screen . A
value of 0 corresponds to NO EVENT .
Integer
0,1,2,3
fixeddeadband
See
Fixed Deadband on the
DNP3 Outstation Settings
screen . Set to “disabled” to disable fixed deadband
reporting for this setpoint .
Integer or
“disabled”
Any non-negative
integer value or
“disabled”
percentdeadband
See
Pct Deadband on the
DNP3 Outstation Settings
screen . Set to “disabled” to disable percent deadband
reporting for this setpoint .
Integer or
“disabled”
Any non-negative
integer value or
“disabled”
scaling
Floating point scaling factor, to be applied as a
multiplication factor to the raw setpoint measurement
before it is sent to the SCADA master . See
Scaling on
DNP3 Outstation Settings
screen .
Float
0 .001 … 1000
<CounterSetPoints>
<countersetpoint/>
</CounterSetPoints>
statuspoint
See
Status Point on the
DNP3 Outstation Settings
screen .
Integer
0 … 19
codedescription
See
Code Description on the
DNP3 Outstation Settings
screen .
Integer
per 461-560
eventclass
See
Class on the
DNP3 Outstation Settings
screen . A
value of 0 corresponds to NO EVENT .
Integer
0,1,2,3
fixeddeadband
See
Fixed Deadband on the
DNP3 Outstation Settings
screen . Set to “disabled” to disable fixed deadband
reporting for this setpoint .
Integer or
“disabled”
Any non-negative
integer value or
“disabled”
percentdeadband
See
Pct Deadband on the
DNP3 Outstation Settings
screen . Set to “disabled” to disable percent deadband
reporting for this setpoint .
Integer or
“disabled”
Any non-negative
integer value or
“disabled”
<BinaryOutputSetPoints>
<binaryoutputsetpoint/>
</BinaryOutputSetPoints>
statuspoint
See
Status Point on the
DNP3 Outstation Settings
screen .
Integer
0 … 8
codedescription
See
Code Description on the
DNP3 Outstation Settings
screen .
Integer
Per Instruction
Sheet 461-560