Negative Sequence
The
Negative Sequence
element trips the IntelliRupter fault interrupter when the
negative sequence component of the three-phase elements exceeds the pickup value for
the time value set by the
Inverse Curve or Definite Time
settings.
Negative Sequence Check box—
Select to configure this element.
Inverse Segment—
Select from the drop-down list of inverse curve names or select the
None
option. When the
None
option is selected, only the
Definite Time
settings will
be used.
Min. Trip—
This is the current (in primary amperes) at which the inverse curve begins
timing. (Range: 6-16,000; Step: 1) The stated maximum is for 15-kV IntelliRupter fault
interrupters; 27-kV and 38-kV are limited to 12,500 amps maximum.
Min. Time—
This is the time (in seconds) defining the fastest response of the inverse
curve portion of the TCC curve. (Range: 0.000-100.000; Step: 0.001)
Time Mult—
This is the time modifier for the inverse curve. (Range: .001-15.00; Step: 0.01)
Time Adder—
This is the time modifier for the inverse curve. (Range: -10.000-100.000;
Step: 0.001)
Low Cutoff—
This is the current (in primary amperes) at which the TCC curve
begins timing. This value must be equal to or greater than the lowest pickup value of
the inverse curve, the
Definite Time 1
element, and the
Definite Time 2
element.
(Range: 6-16,000; Step: 1) Also see the
Maximum Interrupting Current
setting on the
Setup>General>Site-Related
screen.
Reset—
Select the reset method for the inverse curve from the drop-down list:
D/T
(Definite Time) or
E/M
(Electromechanical) mode.
Reset Time—
If the Definite Time reset method is selected, enter the time delay for the
reset (in seconds). (Range: 0.000-600.000; Step: 0.001)
Definite Time 1 Min. Trip—
This is the current (in primary amperes) at which the
Definite Time 1
element picks up. (Range: 6-16,000; Step: 1) The stated maximum is
for 15-kV IntelliRupter fault interrupters; 27-kV and 38-kV are limited to 12,500 amps
maximum.
Definite Time 1 Min. Time—
This is the time delay (in seconds) after which the
Definite
Time 1
element trips. (Range: 0.000-600.000; Step: 0.001)
Definite Time 2 Min. Trip—
This is the current (in primary amperes) at which the
Definite Time 2
element picks up. (Range: 6-16,000; Step: 1) The stated maximum is
for 15-kV IntelliRupter fault interrupters, 27-kV and 38-kV are limited to 12,500 amps
maximum.
Definite Time 2 Min. Time—
This is the time delay (in seconds) after which the
Definite
Time 2
element trips. (Range: 0.000-600.000; Step: 0.001)
S&C Instruction Sheet 766-530 65
Protection Setup