Reset Time—
When the
Definite Time
reset mode is selected, enter the time delay for
the reset (in seconds). (Range: 0.000-6000.000; Step: 0.001)
Definite Time 1 Min. Trip—
This is the current (in primary amperes) at which the
Definite Time 1
element picks up. (Range: 3-16,000; Step: 1) The stated maximum
is for 15-kV IntelliRupter fault interrupters; 27-kV and 38-kV models are limited to
12,500 amps maximum.
Definite Time 1 Min. Time—
This is the time delay (in seconds) after which the
Definite Time 1
element trips. (Range: 1.000-6000.000; Step: 0.001)
Definite Time 2 Min. Trip—
This is the current (in primary amperes) at which the
Definite Time 2
element picks up. (Range: 3-16,000; Step: 1) The stated maximum
is for 15-kV IntelliRupter fault interrupters; 27-kV and 38-kV models are limited to
12,500 amps maximum.
Definite Time 2 Min. Time—
This is the time delay (in seconds) after which the
Definite Time 2
element trips. (Range: 1.000-600.000; Step: 0.001)
Ground Trip Block Radio Buttons
When the
Allow Ground Trip Block
mode is active (the default), the
Ground Trip
element blocks commands from SCADA and IntelliLink software, and the manual
GROUND TRIP BLOCK lever will operate normally. The
Ground Trip
element will be
blocked even in the
Hot Line Tag
profile.
When the
Do not allow Ground Trip Block
setting is active, the
Ground
element will be implemented as configured for the
Hot Line Tag
profile, overriding any
Ground Trip Block
commands from SCADA, IntelliLink software, or a manual GROUND
TRIP BLOCK lever operation. This override only applies to the
Hot Line Tag
profile.
92 S&C Instruction Sheet 766-530
Protection Setup