Use of Self-Address 65532
NOTICE
Disabling the
Use of Self-Address setting can prevent the control from
communicating with IntelliLink software . If communication with the control is
lost, you must know the
Local Device DNP Address setting, connect through a
remote IntelliLink software connection, and re-enable the
Use of Self-Address
setting to connect locally . Wi-Fi will not work if the
Use of Self-Address setting
is disabled . If the local DNP address is not known and the
Use of Self-Address
setting is disabled, the control will require reprogramming at the factory to
re-establish access to the control .
This setting is present to comply with the DNP standard. Care must be used when deciding
to change the default. Options are the
Disabled
setting, which blocks the use of DNP
Address 65532, and the
Enabled
setting, which allows the use of DNP Address 65532.
Default is enabled.
Limit Unknown Master Functionality
NOTICE
Enabling this feature prevents unknown master stations from making any
configuration changes . When the
Limit Unknown Master Functionality setting
is enabled, at least one master other than the SCADA master must be enabled .
When this feature is enabled, the only way to connect with the control (to make any
changes or disable this feature) is with IntelliLink Remote software and a computer
set to the configured DNP address of the enabled master that is not the SCADA
master . The control must be returned to the factory to be reset to the factory default
when the DNP address of the master is unknown .
The default is the
Disabled
setting to allow master station addresses to be entered
into the configuration. After those addresses have been entered, this parameter may be
enabled and a configured master station address used to complete the configuration
process.
When enabled, a master/peer station not included in the configuration of this control
is prevented from writing to or controlling it. Master/peer stations configured in this
control include any of the six Master Station DNP addresses and team members config-
ured on the
Setup>Restoration>IntelliTeam SG>Team Summary
screen. The default
is the
Disabled
setting.
Enforce Master Association
The primary identification for a master station is its DNP address. When a master sends
DNP requests to a control and this setting is enabled, the master’s port code (i.e. TCP, UDP,
or serial), IP address (when the port code is TCP or UDP), and DNP address must match
the data configured for that master station in the control. DNP requests are ignored when
this setting is enabled and the IP address and port code do not match the configured data.
When this setting is disabled, the IP address and port code are ignored, and only the DNP
address is checked and validated with the control configuration. Note that configuring
the
Failover IP Address
setting is optional; when the
Enforce Master Association
feature is enabled, the master station IP address must match either the configured
IP
Address
or the
Failover IP Address
setting.
146 S&C Instruction Sheet 766-530