S&C Instruction Sheet 766-557 13
Step 3
Select the
Change Setup...
button. This will launch the
IntelliLink Options
menu. Navigate to the
Communications
tab, shown in Figure 10. Change the
connection from
UDP/IP to
Serial
and then select the correct
COM Port
. In this case the
port is COM1. The Baud Rate should be set at 57600. No other options should be changed.
Figure 10. IntelliLink Options dialog window.
Step 4
When you have set the communications parameters on the
Options
window, click the
Save & Exit
button.
Step 5
After the
Options
window closes, the
Connect
window will be visible. Click the
Retry
button. See Figure 9. The IntelliLink software will attempt to establish a connection using
the new communication parameters.
Depending on the state of firmware in the control, you may receive a warning or an
error message once a connection has been established.
If you receive an error message or were unable to download firmware through the
Wi-Fi connection to upgrade your control, follow the instructions for
Reloading Firmware
with Download Utility
.
If you performed this procedure to determine if your control is operational and did
not receive warnings or errors, please contact S&C Electric Company for support. Your
problem is probably not related to control firmware.
Reloading control firmware should only be started after an attempt to connect to the con-
trol with the IntelliLink software has generated errors or warning messages that indicate
incorrect versions or maintenance mode conditions.
Step 1
In order to avoid communication conflicts, close any open instances of the IntelliLink
software before launching
Download Utility
(DU).
Reloading Firmware
with Download Utility
Serial Connection—Rev. 3.4.x and Earlier