16    S&C Instruction Sheet 766-557 

After control firmware has been successfully loaded, it is recommended that you verify 
that the control is operating correctly, by using the IntelliLink software. 

Step 1

After closing the update window the IntelliLink software will prompt you to log in. Enter 
the appropriate 

Use Name

 and 

Password

Step 2

On the IntelliRupter 

Operation

 screen, check the 

Control Status

 in the upper right hand 

corner. Verify that the control is in the 

Okay

 state. If there are any alarms, warnings, or 

errors—please contact S&C Electric Company.

Step 3

Check the 

Setup

 > 

General

 > 

Revisions

 screen, shown in Figure 14, to see that the cor-

rect firmware has been installed.

Verification of 

Correct Operation

Figure 14. The IntelliRupter Setup > General > Revisions screen.

  After you complete verification, change the communication parameters of IntelliLink 
back to the default settings. 

Step 4

Locate the 

Tools

 menu option at the top of the screen. The communication parameters 

are on the 

Tools > Options

 menu. See Figure 15. Change the 

Connection Type

 to 

UDP/

IP

 and then click the 

Save & Exit 

button. Close the IntelliLink software.

Step 5

Disconnect the serial cable from the jumper, and reconnect the jumper to the 

Wi-Fi Serial 

to Comm

 connector on the Docking Station. 

The Control and Communication Modules should now correctly respond to a 

LinkStart

 

connection attempt.

Serial Connection—Rev. 3.4.x and Earlier

Содержание IntelliRupter PulseCloser SDA-4650R2

Страница 1: ...mation Understanding Safety Alert Messages 3 Following Safety Instructions 3 Replacement Instructions and Labels 3 Overview 4 Setup 5 Establishing Wi Fi Connection 7 Serial Connection with a Docking S...

Страница 2: ...ontained in S C s standard conditions of sale as set forth in Price Sheet 150 applies to IntelliRupter fault interrupter and its associated options except for the control group the protection and cont...

Страница 3: ...E NOTICE identifies important procedures or requirements that can result in product or property damage if instructions are not followed Following Safety Instructions If you do not understand any porti...

Страница 4: ...ffic between the protection and control module and the communication module using either a secure Wi Fi connection to your personal computer or a direct connection to your serial port equipped persona...

Страница 5: ...the docking station to com municate with the protection and control module instead of using the Wi Fi connection a Remove the factory installed Wi Fi Serial to Control Wi Fi Serial to Comm jumper from...

Страница 6: ...ed settings stored in the base memory module Step 9 Turn on the docking station power switch The red lamp on the docking station will light And the status indicator on the protection and control modul...

Страница 7: ...re or LinkStart icon or select Program Start S C Electric LinkStart V3 on the personal computer The LinkStart connection screen will appear See Figure 2 Figure 2 LinkStart connection screen If the bas...

Страница 8: ...s dim to bright while Wi Fi connection is being established After IntelliRupter fault interrupter recognizes the wake up message and its source it will proceed with authentication Encrypted messages a...

Страница 9: ...m II Automatic Restoration System and loop resto ration can be entered into the protection and control module while it is connected to the docking station But only the settings actually suitable for t...

Страница 10: ...he module is installed in the IntelliRupter fault interrupter base select Setup General Tab IntelliRupter See Figure 6 Select On Next Power up Use Settings From Control Remember to select Setup Valida...

Страница 11: ...n Serial Cable PC Computer loaded with the latest IntelliRupter Fault Interrupter Software Step 1 Power the Docking Station and check that the red LED is on Step 2 Locate the serial jumper cable on to...

Страница 12: ...the IntelliLink Setup Software application file Step 2 When the IntelliLink software is launched it is configured by default to connect to the control over a wireless link It automatically attempts t...

Страница 13: ...he control you may receive a warning or an error message once a connection has been established If you receive an error message or were unable to download firmware through the Wi Fi connection to upgr...

Страница 14: ...ut will eventually time out The connection status for DU is displayed in the lower left hand corner See Figure 12 Figure 12 Download Utility connection status shown on the Control Software Loader wind...

Страница 15: ...nge the DNP Settings the Peer Addr or Our Addr settings Use the settings configured in Download Utility Step 5 When you have set all parameters on the Control Software Loader Communication Setup tab c...

Страница 16: ...een shown in Figure 14 to see that the cor rect firmware has been installed Verification of Correct Operation Figure 14 The IntelliRupter Setup General Revisions screen After you complete verification...

Страница 17: ...file Step 2 When the IntelliLink software is launched it is configured by default to connect to the control over a wireless link It automatically attempts to establish this connection Wait for the con...

Страница 18: ...Make sure the Protocol is DNP Change if needed Change the RTU to self or 65532 Change the connection from UDP IP to Serial and then select the correct COM Port In this case the port is COM5 The Baud...

Страница 19: ...nnect to the con trol with the IntelliLink software has generated errors or warning messages that indicate incorrect versions or maintenance mode conditions Step 1 Connect with the IntelliLink softwar...

Страница 20: ...l appear It is recommended that you select the Yes button unless instructed otherwise by an S C representative Figure 23 Confirmation dialog box Step 5 After the software components have been installe...

Страница 21: ...Software Versions screen shown in Figure 25 to see that the correct firmware has been installed Verification of Correct Operation Figure 25 The IntelliRupter Setup General Software Versions screen Aft...

Страница 22: ...switch is turned off power cannot be turned on during that time Step 1 Turn off the docking station power switch Step 2 Carefully disconnect the protection and control module and the communication mod...

Страница 23: ...ion Main screen The original Docking Station Catalog Number SDA 4650R1 was shipped with Base Memory Module BMM SDA 4781 which simulates the older IntelliRupter fault inter rupter without a Ground Trip...

Страница 24: ......

Отзывы: