S&C Instruction Sheet 766-557    5

Setup

Step 1

Set up the docking station on a sturdy work surface. If Global Positioning System opera-
tion is to be checked, place the docking station near a window, so that satellite signals 
can be received by the user-furnished GPS antenna.

Step 2

Connect the power cord to the docking station. Then plug the power cord into an ac outlet.

 

Step 3

If a SpeedNet Radio is installed:

 Insert the “Radio Ethernet to Control / Radio Ethernet 

to Comm” jumper into the docking station. 

Step 4

If you wish to directly connect your personal computer to the docking station to com-
municate with the protection and control module, instead of using the Wi-Fi connection:

 

a.  Remove the factory-installed “Wi-Fi Serial to Control / Wi-Fi Serial to Comm” jumper 

from the docking station.

b.  Plug the computer into the “Wi-Fi Serial to Control” port.

Step 5

Carefully attach the protection and control module to the docking station. Make sure that 
the connector guide pins are aligned properly, then insert them fully.

Step 6

Carefully attach the communication module to the docking station. Make sure that the 
connector guide pins are aligned properly, then insert them fully.

Step 7

If serial traffic between the protection and control module and the radio is to be moni-
tored through a DNP test set:

 Plug the DNP test set into the “RX” port.

Содержание IntelliRupter PulseCloser SDA-4650R2

Страница 1: ...mation Understanding Safety Alert Messages 3 Following Safety Instructions 3 Replacement Instructions and Labels 3 Overview 4 Setup 5 Establishing Wi Fi Connection 7 Serial Connection with a Docking S...

Страница 2: ...ontained in S C s standard conditions of sale as set forth in Price Sheet 150 applies to IntelliRupter fault interrupter and its associated options except for the control group the protection and cont...

Страница 3: ...E NOTICE identifies important procedures or requirements that can result in product or property damage if instructions are not followed Following Safety Instructions If you do not understand any porti...

Страница 4: ...ffic between the protection and control module and the communication module using either a secure Wi Fi connection to your personal computer or a direct connection to your serial port equipped persona...

Страница 5: ...the docking station to com municate with the protection and control module instead of using the Wi Fi connection a Remove the factory installed Wi Fi Serial to Control Wi Fi Serial to Comm jumper from...

Страница 6: ...ed settings stored in the base memory module Step 9 Turn on the docking station power switch The red lamp on the docking station will light And the status indicator on the protection and control modul...

Страница 7: ...re or LinkStart icon or select Program Start S C Electric LinkStart V3 on the personal computer The LinkStart connection screen will appear See Figure 2 Figure 2 LinkStart connection screen If the bas...

Страница 8: ...s dim to bright while Wi Fi connection is being established After IntelliRupter fault interrupter recognizes the wake up message and its source it will proceed with authentication Encrypted messages a...

Страница 9: ...m II Automatic Restoration System and loop resto ration can be entered into the protection and control module while it is connected to the docking station But only the settings actually suitable for t...

Страница 10: ...he module is installed in the IntelliRupter fault interrupter base select Setup General Tab IntelliRupter See Figure 6 Select On Next Power up Use Settings From Control Remember to select Setup Valida...

Страница 11: ...n Serial Cable PC Computer loaded with the latest IntelliRupter Fault Interrupter Software Step 1 Power the Docking Station and check that the red LED is on Step 2 Locate the serial jumper cable on to...

Страница 12: ...the IntelliLink Setup Software application file Step 2 When the IntelliLink software is launched it is configured by default to connect to the control over a wireless link It automatically attempts t...

Страница 13: ...he control you may receive a warning or an error message once a connection has been established If you receive an error message or were unable to download firmware through the Wi Fi connection to upgr...

Страница 14: ...ut will eventually time out The connection status for DU is displayed in the lower left hand corner See Figure 12 Figure 12 Download Utility connection status shown on the Control Software Loader wind...

Страница 15: ...nge the DNP Settings the Peer Addr or Our Addr settings Use the settings configured in Download Utility Step 5 When you have set all parameters on the Control Software Loader Communication Setup tab c...

Страница 16: ...een shown in Figure 14 to see that the cor rect firmware has been installed Verification of Correct Operation Figure 14 The IntelliRupter Setup General Revisions screen After you complete verification...

Страница 17: ...file Step 2 When the IntelliLink software is launched it is configured by default to connect to the control over a wireless link It automatically attempts to establish this connection Wait for the con...

Страница 18: ...Make sure the Protocol is DNP Change if needed Change the RTU to self or 65532 Change the connection from UDP IP to Serial and then select the correct COM Port In this case the port is COM5 The Baud...

Страница 19: ...nnect to the con trol with the IntelliLink software has generated errors or warning messages that indicate incorrect versions or maintenance mode conditions Step 1 Connect with the IntelliLink softwar...

Страница 20: ...l appear It is recommended that you select the Yes button unless instructed otherwise by an S C representative Figure 23 Confirmation dialog box Step 5 After the software components have been installe...

Страница 21: ...Software Versions screen shown in Figure 25 to see that the correct firmware has been installed Verification of Correct Operation Figure 25 The IntelliRupter Setup General Software Versions screen Aft...

Страница 22: ...switch is turned off power cannot be turned on during that time Step 1 Turn off the docking station power switch Step 2 Carefully disconnect the protection and control module and the communication mod...

Страница 23: ...ion Main screen The original Docking Station Catalog Number SDA 4650R1 was shipped with Base Memory Module BMM SDA 4781 which simulates the older IntelliRupter fault inter rupter without a Ground Trip...

Страница 24: ......

Отзывы: