22 S&C Instruction Sheet 766-540
SCADA Operation
Remote Operation Button
When line work is planned, the IntelliRupter fault interrupter operation can be blocked
via SCADA or remotely with IntelliLink software. To block remote operation, set this to
the
Disabled
state. See Figure 12.
NOTICE
When the
Remote Operation mode is set to the Disabled state with a SCADA
command or a remote IntelliLink software command—the
Remote Operation mode
can only be set to the
Enabled state by a Wi-Fi command at the IntelliRupter fault
interrupter site .
A number of DNP control points are available to remotely operate the IntelliRupter
fault interrupter with SCADA commands.
DNP points are mapped to conform to the SCADA system requirements. See
Instruction Sheet 766-530, “IntelliRupter® PulseCloser® Fault Interrupter:
Protection
and Communication Setup Instr uctions,
” and Instruction Sheet 766 -560,
“I ntel l iRupter® P u lseCloser® Fau lt I nter r upter:
DN P Po int s L i st a n d
Implementation.”
Enabling SCADA
Operation
Figure 12. Enabling SCADA operation on the Operation screen.