16 S&C Instruction Sheet 766-540
Operation Using IntelliLink® Setup Software
After the IntelliRupter fault interrupter and the computer have been configured and set
up for Wi-Fi communication, connection is automatically accomplished with IntelliLink
Setup Software.
To connect to an IntelliRupter fault interrupter with IntelliLink Setup Software, see
the “Wi-Fi Connection to an IntelliRupter with IntelliLink” section in Instruction Sheet
766-571, “IntelliRupter® PulseCloser® Fault Interrupter:
Software Installation
.”
Starting IntelliLink
Setup Software
NOTICE
With software later than version 7 .3 .100, the default passwords for all user
accounts, including the Admin account, must be changed before the IntelliLink
software can connect to and configure a control . See Instruction Sheet
766-530, “IntelliRupter® PulseCloser® Fault Interrupter:
Protection and
Communication Setup,
” for more information .
After password verification, the
Operation
screen opens. It presents IntelliRupter fault
interrupter status information and is used to operate the device. See Figure 11. User-
assigned IntelliRupter fault interrupter identification information, the
Connected to:
and
Location:
options, are shown at the top of every screen.
An electronic representation of the IntelliRupter fault interrupter OPEN/CLOSE/
READY lever side is shown. Poles 1, 2, and 3 are displayed left to right (in this case labeled
1, 2, and 3). The upper terminal pads are labeled Y1, Y2, Y3, and the lower terminal pads
are labeled X1, X2, X3.
Phase-to-ground or phase-to-phase voltage at each terminal pad is shown on the
associated pole-unit, and the voltage units are user-assigned.
NOTICE
Because the IntelliRupter fault interrupter voltage sensors are high-impedance
sensing devices, they will indicate a presence of voltage on the Y-side terminals
when the optional disconnect is installed and open . The voltage reading is an
artifact of leakage current resulting from parasitic capacitance; therefore, the
readings can be quite variable from unit to unit and pole to pole . Humidity and other
weather-related conditions add to the variability at a given unit .
Figure 11. The IntelliRupter fault interrupter Operation screen.
Operation Screen