background image

12

    S&C Instruction Sheet 1011-510 

Grounded Wye Banks

Ç

 WARNING

Do not enable communications by connecting radios, fiber optic cables, or dedicated 
phone lines until this is called out in the instructions.

  Before attempting to access an existing installation, check carefully for visible 
or audible signs of electrical or physical malfunction (do this before touching or 
operating the BankGuard Plus Control or any other part of the installation). These 
warning signs include such things as smoke, fire, open fuses, crackling noises, loud 
buzzing, etc. If a malfunction is suspected, treat all components of the installation, 
including the control and associated mounting hardware, as if they were elevated 
to primary (HIGH) voltage.

  You must follow the sequence of installation steps outlined in this instruction sheet 
to insure a safe and successful BankGuard Plus Control installation.

Step 2

  Make the connections to the terminal strips on the back of the control.

The BankGuard Plus Control includes numbered terminal strips on the back of the 
enclosure for external control-wiring connections. See Figure 1, Table 1, and the 
electrical diagrams at the end of this instruction sheet.

  Using the terminal strip illustrations, make the following connections:

A.  The station ground to TB2-1.

B.  The output terminals of three S&C 30-Volt-Ampere Potential Devices to TB1-9, 

TB1-10, TB2-11, and TB2-12 (phase voltage return). The potential devices should 
have a system voltage rating at least equal to the voltage appearing between the 
intermediate tap points and ground, multiplied by 

3.

C.  The opening circuit of the bank switch operator, to TB2-4 and TB2-5.

D.  The closing circuit of the bank switch operator, to TB2-2 and TB2-3.

E.   The control device power source (48-250 Vdc, 100-240 Vac, 50 or 60 Hz, as 

appropriate), to TB2-9 and TB2-10. Observe polarity if dc.

F.   The “b” contact of the auxiliary switch on the bank switch operator to TB2-6. 

Terminal TB2-10 may be used as the source for the wetting voltage. Set this 
contact to open near the fully-closed position of the capacitor bank switching 
device.

G.   The space heater source, where applicable (120 Vac/60 Hz or 240 Vac/60 Hz).

H.   Alarm circuit (optional) to terminals TB1-2 and TB1-3 for normally closed alarm 

contacts. Use terminals TB1-4 and TB1-5 for normally open contacts.

I.   If unbalance compensation is required, connect the output of a 30-Volt-Ampere 

Potential Device to TB1-11 (Star voltage) and TB2-12 (Star voltage return).

Step 3

  Check the circuits connecting the potential devices to the control device.

The circuits connecting the potential devices to the BankGuard Plus control must 
be free of variable loads, variable voltage drops, and ground loops. This insures that 
the monitored voltages accurately represent the magnitude and phase angle of the 
bus voltages. Some possible errors affecting unbalance compensation are:

• 

Unbalanced or variable loading of the potential devices. (Note that this means 
that station service transformers are not suitable.)

• 

Control-wiring voltage drops between the potential devices and the control. 
To minimize voltage drops, connect the potential devices and the control with 
dedicated circuits that are adequately sized.

• 

Example—

A 1 amp current flowing through 1000 feet of #10 AWG wire results 

in a 1 V drop in the voltage signal. This may be enough to affect the performance 
of the protection scheme.

Содержание BankGuard PLUS

Страница 1: ...tion Checklist 4 In Shop Setup 4 Ungrounded Wye Banks Installation 5 Test the Control 10 Grounded Wye Banks Installation 11 Test the Control 13 Ungrounded Wye Shunt Reactors Installation 14 Test the C...

Страница 2: ...nkGuard Plus Designate a location where you can easily retrieve and refer to this publication Warranty SPECIAL WARRANTY PROVISIONS The standard warranty contained in seller s standard conditions of sa...

Страница 3: ...OTICE identifies important procedures or requirements that can result in product or property damage if instructions are not followed Following Safety Instructions If you do not understand any portion...

Страница 4: ...e problems that can occur uring installation NOTE Although it is possible use the faceplate buttons and LCD for the initial setup of the control using the IntelliLink software makes the process faster...

Страница 5: ...rds that may be involved This document is written only for such qualified persons and is not a substitute for adequate training and experience in safety procedures for accessing high voltage equipment...

Страница 6: ...BankGuard Plus Control includes numbered terminal strips on the back of the enclosure for external control wiring connections See Figure 1 Table 1 and the electrical diagrams at the end of this instru...

Страница 7: ...B1 11 Star voltage TB1 12 Star voltage return TB2 A 2nd Lockout O O O C TB2 B 2nd Lockout O O O C TB2 1 Chassis ground TB2 2 Lockout C C C O TB2 3 Lockout C C C O TB2 4 Lockout O O O C TB2 5 Lockout O...

Страница 8: ...C 30 Volt Ampere Potential Device s to TB1 9 TB1 10 DB2 11 and TB2 12 phase voltage return Step 4 If necessary connect the potential devices or voltage transformers used for unbalance compensation If...

Страница 9: ...e to ground voltage relationships for all but fault conditions The circuits connecting the potential devices voltage transformers to the BankGuard Plus Control must be free of variable loads variable...

Страница 10: ...rmation on the LCD If password protection is enabled press the NEXT button again to start scroll ing through password values If the display is blank see the Troubleshooting Instruction Sheet 1011 550...

Страница 11: ...ap point and ground should equal the number of series groups between the tap point and the line For capacitor banks with an odd number of series groups per phase the number of series groups between th...

Страница 12: ...ircuit of the bank switch operator to TB2 4 and TB2 5 D The closing circuit of the bank switch operator to TB2 2 and TB2 3 E The control device power source 48 250 Vdc 100 240 Vac 50 or 60 Hz as appro...

Страница 13: ...INDICATOR or ALARM INDICATOR LED turns ON press the corresponding RESET button to clear it B Press the ENTER button to test the faceplate LEDs All LEDs should turn ON for 2 seconds C Press the NEXT b...

Страница 14: ...hazards that may be involved This document is written only for such qualified persons and is not a substitute for adequate training and experience in safety procedures for accessing high voltage equi...

Страница 15: ...p 3 Step 3 If necessary connect the potential devices or voltage transformers used for unbalance compensation If the BankGuard Plus Control uses the optional unbalance compensation feature you must al...

Страница 16: ...This insures that the monitored voltages accurately represent the magnitude and phase angle of the bus voltages Some possible errors affecting unbalance compensation are Differences in the effective...

Страница 17: ...INDICATOR or ALARM INDICATOR LED turns ON press the corresponding RESET button to clear it B Press the ENTER button to test the faceplate LEDs All LEDs should turn ON for 2 seconds C Press the NEXT b...

Страница 18: ...BankGuard Plus installation S C Electric Company supports the BankGuard Plus Control with a variety of communi cations hardware options S C SpeedNet Radio UtiliNet Radio Cellnet Radio Microwave Data...

Страница 19: ...S C Instruction Sheet 1011 510 19 Installation and Connection Drawings...

Страница 20: ...20 S C Instruction Sheet 1011 510 Installation and Connection Drawings...

Страница 21: ...S C Instruction Sheet 1011 510 21 Installation and Connection Drawings...

Страница 22: ...22 S C Instruction Sheet 1011 510 Installation and Connection Drawings...

Страница 23: ...S C Instruction Sheet 1011 510 23 Installation and Connection Drawings...

Страница 24: ...Printed in U S A...

Отзывы: