background image

   

S&C Instruction Sheet 1011-510

   

9

Ungrounded Wye Banks

any secondary of a high-impedance grounding transformer. The voltage rating 
of the voltage transformer should match the secondary voltage rating of the 
grounding transformer. Be sure that the grounding transformer is connected 
to the station bus from which the capacitor bank is tapped. (The grounding 
transformer maintains the stability of phase-to-ground voltage relationships for 
all but fault conditions.)

C. 

To detect and compensate for the inherent capacitor bank imbalance Plus the 
system voltage imbalance, in applications where the source is grounded, 

con-

nect to one of the following:

• 

Three S&C 30-Volt-Ampere Potential Devices rated for full system voltage, 
each connected to a phase of the station bus from which the capacitor bank 
is tapped.

• 

Three voltage transformers, connected to the station bus, groundedwye/
grounded-wye.

D. 

To detect and compensate for the inherent capacitor bank imbalance Plus the 
system voltage imbalance, in applications where the source is a delta-connected 
tertiary transformer winding,

 you must connect to three 1:1 voltage trans-

formers, each of which is then connected to the secondary of a high-impedance 
grounding transformer. The voltage ratings of the voltage transformers should 
match the secondary voltage rating of the grounding transformer. Be sure that the 
grounding transformer is connected to the station bus from which the capacitor 
bank is tapped. (The grounding transformer maintains the stability of phase-to-
ground voltage relationships for all but fault conditions.)

  The circuits connecting the potential devices/voltage transformers to the 
BankGuard Plus Control must be free of variable loads, variable voltage drops, 
and ground loops. This insures that the monitored voltages accurately represent 
the magnitude and phase angle of the bus voltages. Some possible errors affect-
ing unbalance compensation are:

• 

Differences in the effective voltage ratios among the three S&C 30-Volt-
Ampere Potential Devices/voltage transformers used to obtain system-
derived voltages.

• 

Unbalanced or variable loading of the potential devices/voltage transformers 
used to obtain system-derived voltages. (Note that this means that station 
service transformers are not suitable.)

• 

Control-wiring voltage drops between the potential devices/voltage trans-
formers and the control. To minimize voltage drops, connect the potential 
devices/voltage transformers and the control with dedicated circuits that 
are adequately sized.

 Example

—A 1 amp current flowing through 1000 feet of #10 AWG wire 

results in a 1 V drop in the voltage signal. This may be enough to affect the 
performance of the protection scheme.

• 

Induced voltages in control wiring. Proper shielding is important.

• 

Ground loops caused by differences in voltage between the grounding 
points for the capacitor bank neutral-to-ground potential device/voltage 
transformer and those for the potential devices/voltage transformers used 
to obtain system-derived voltages. Preferably, the secondaries of all the 
potential devices/voltage transformers should be grounded at one point 
(per proposed ANSI C57.13.3, “Guide for the Grounding of Instrument 
Transformer Secondary Circuits and Cases”).

Содержание BankGuard PLUS

Страница 1: ...tion Checklist 4 In Shop Setup 4 Ungrounded Wye Banks Installation 5 Test the Control 10 Grounded Wye Banks Installation 11 Test the Control 13 Ungrounded Wye Shunt Reactors Installation 14 Test the C...

Страница 2: ...nkGuard Plus Designate a location where you can easily retrieve and refer to this publication Warranty SPECIAL WARRANTY PROVISIONS The standard warranty contained in seller s standard conditions of sa...

Страница 3: ...OTICE identifies important procedures or requirements that can result in product or property damage if instructions are not followed Following Safety Instructions If you do not understand any portion...

Страница 4: ...e problems that can occur uring installation NOTE Although it is possible use the faceplate buttons and LCD for the initial setup of the control using the IntelliLink software makes the process faster...

Страница 5: ...rds that may be involved This document is written only for such qualified persons and is not a substitute for adequate training and experience in safety procedures for accessing high voltage equipment...

Страница 6: ...BankGuard Plus Control includes numbered terminal strips on the back of the enclosure for external control wiring connections See Figure 1 Table 1 and the electrical diagrams at the end of this instru...

Страница 7: ...B1 11 Star voltage TB1 12 Star voltage return TB2 A 2nd Lockout O O O C TB2 B 2nd Lockout O O O C TB2 1 Chassis ground TB2 2 Lockout C C C O TB2 3 Lockout C C C O TB2 4 Lockout O O O C TB2 5 Lockout O...

Страница 8: ...C 30 Volt Ampere Potential Device s to TB1 9 TB1 10 DB2 11 and TB2 12 phase voltage return Step 4 If necessary connect the potential devices or voltage transformers used for unbalance compensation If...

Страница 9: ...e to ground voltage relationships for all but fault conditions The circuits connecting the potential devices voltage transformers to the BankGuard Plus Control must be free of variable loads variable...

Страница 10: ...rmation on the LCD If password protection is enabled press the NEXT button again to start scroll ing through password values If the display is blank see the Troubleshooting Instruction Sheet 1011 550...

Страница 11: ...ap point and ground should equal the number of series groups between the tap point and the line For capacitor banks with an odd number of series groups per phase the number of series groups between th...

Страница 12: ...ircuit of the bank switch operator to TB2 4 and TB2 5 D The closing circuit of the bank switch operator to TB2 2 and TB2 3 E The control device power source 48 250 Vdc 100 240 Vac 50 or 60 Hz as appro...

Страница 13: ...INDICATOR or ALARM INDICATOR LED turns ON press the corresponding RESET button to clear it B Press the ENTER button to test the faceplate LEDs All LEDs should turn ON for 2 seconds C Press the NEXT b...

Страница 14: ...hazards that may be involved This document is written only for such qualified persons and is not a substitute for adequate training and experience in safety procedures for accessing high voltage equi...

Страница 15: ...p 3 Step 3 If necessary connect the potential devices or voltage transformers used for unbalance compensation If the BankGuard Plus Control uses the optional unbalance compensation feature you must al...

Страница 16: ...This insures that the monitored voltages accurately represent the magnitude and phase angle of the bus voltages Some possible errors affecting unbalance compensation are Differences in the effective...

Страница 17: ...INDICATOR or ALARM INDICATOR LED turns ON press the corresponding RESET button to clear it B Press the ENTER button to test the faceplate LEDs All LEDs should turn ON for 2 seconds C Press the NEXT b...

Страница 18: ...BankGuard Plus installation S C Electric Company supports the BankGuard Plus Control with a variety of communi cations hardware options S C SpeedNet Radio UtiliNet Radio Cellnet Radio Microwave Data...

Страница 19: ...S C Instruction Sheet 1011 510 19 Installation and Connection Drawings...

Страница 20: ...20 S C Instruction Sheet 1011 510 Installation and Connection Drawings...

Страница 21: ...S C Instruction Sheet 1011 510 21 Installation and Connection Drawings...

Страница 22: ...22 S C Instruction Sheet 1011 510 Installation and Connection Drawings...

Страница 23: ...S C Instruction Sheet 1011 510 23 Installation and Connection Drawings...

Страница 24: ...Printed in U S A...

Отзывы: