38 S&C Instruction Sheet 1041-540
Using IntelliLink Software Without Data
Follow this procedure to prepare a setpoint configuration for a switch control in the field
while there access to a comparable device is not available:
STEP 1.
Connect to the snapshot. For details, see the “Viewing a Snapshot” section on
page 37.
STEP 2.
Change the configuration settings in the snapshot as needed. For details, see
the Instruction Sheet 1041-530.
STEP 3.
At any
IntelliLink
screen, click the on the
Setup Menu
button.
STEP 4.
At the
SETUP MENU
screen, click the on the
Save Data
button.
STEP 5.
In the Save Setpoints dialog box, choose a file name and location for this
configuration, and then click on the
Save
button.
If a location is not specified, the file is saved to the same directory as the
program files for this switch control. For example, the default location for
SNCD-S0X report files is C:\ELine\SNCD-S0X\. The extension “.CFG” is added
automatically.
Note:
This process does not save the Physical Location on the
SETUP: Miscellaneous
screen, the Communications RTU Address on the
SETUP: Communications
screen,
or the sensor configuration data on the
SETUP: Sensor Configuration
screen, if
applicable.
Creating a
Configuration
(CFG) File