22    S&C Instruction Sheet 1041-540

Switch Control Operation

(e)  If the 

Sectionalizer Reset and Extended Voltage Loss Time

 timer expires 

before the counter reaches the appropriate 

Recloser Counts to Trip

 value, the 

switch control resets the counter to zero. Later voltage losses are considered 
part of a different reclose sequence. However, if three-phase voltage is not 
present when the timer expires, an 

Extended Voltage Loss

 condition exists 

and the switch control opens the switch.

If the counter reaches the setpoint value before the timer expires, and the problem 

was a load-side fault, the control trips open the switch.

Note: 

When the 

Fault Current Required Before First/All Voltage Loss(es)

 mode 

is set to the 

All

 setting, the switch will not trip open unless all voltage losses were pre-

ceded by fault current. However, it may still operate based on the 

Recloser Counts to 

Trip, Voltage Loss Only

 setpoint. See the Setup Instruction Sheet 1041-530 for details.

If the counter reaches the setpoint value before the timer expires, and the problem 

was a source-side fault, the control notes the events but does not trip open the switch.

To enable 

Sectionalizing

 mode:

STEP  1.  

In the

 Features Enabled

 field on the 

SETUP: Automatic Operation

 screen, 

select a combination that includes “Sectionalizing.”

STEP  2.  

If desired, at the 

SETUP: Automatic Operation 

screen, set the S

uccessful 

Reclose Reset Time

 value to coordinate with the reclosers.

STEP  3.  

Use either the faceplate automatic operation ENABLE/DISABLE switch or a 
SCADA command to enable automatic operation of the switch control.

 If the 

Phase Loss Protection 

feature is enabled, the switch control trips open the 

switch in response to a persistent 

Phase Imbalance

 condition to prevent damage to 

customer equipment.
When the 

Phase Loss Protection 

feature is enabled, the switch control uses the following 

logic to determine when to trip open the switch:

(a)  When the switch control detects a loss of voltage on one or two phases, it starts 

the 

Phase Loss Protection Time Threshold 

timer.

(b)  If the voltage loss persists, and true RMS current remains below the 

Phase Loss 

Protection Current Threshold

 setpoint until the timer expires, the switch 

control trips open the switch.

(c)  If voltage returns before the timer expires, the switch control terminates the 

timing operation.

(d)  If voltage returns on one phase before the timer expires, but is then lost on 

another phase, the switch control restarts the timer.

Complete the following steps to enable the 

Phase Loss Protection

 feature:

STEP  1.  

In the 

Features Enabled

 field on the 

SETUP: Automatic Operation

 screen, 

select a combination that includes “Phase Loss Protection.”

Phase Loss
Protection

Содержание 5800 Series

Страница 1: ...witches 18 Phase Angle Measurements 18 Overcurrent Fault Voltage Loss Detection 18 Ground Overcurrent Detection 19 Voltage Loss Detection 20 Inrush Restraint 20 Overcurrent and Voltage Loss Events 20...

Страница 2: ...f your 5800 Series Automatic Switch Control Designate a location where you can easily retrieve and refer to this publication Proper Application WARNING The equipment in this publication is only intend...

Страница 3: ...autions are not followed NOTICE NOTICE identifies important procedures or requirements that can result in product or property damage if instructions are not followed Following Safety Instructions If y...

Страница 4: ...IFIEDPERSONS Accesstothe5800Series Automatic Switch Control must be restricted only to qualified persons See the Qualified Persons section on page 2 2 SAFETY PROCEDURES Always follow safe operating pr...

Страница 5: ...aceplate processor board Power supply control I O module ASP module behind the PS IO module Sensor conditioning module behind the PS IO and ASP modules Figure 1 Location of the switch control modules...

Страница 6: ...g the line switches and the switch control It also includes an LCD screen and two DATA SCROLL switches See Figure 2 Figure 2 The 5801 Series control faceplate Note To extend battery carryover time the...

Страница 7: ...of LEDs for Port A and Port B RCV LED Blinks when the switch control detects an incoming character XMT LED Blinks when the switch control sends one or more characters Note Activity on both of these LE...

Страница 8: ...comes lit when the switch control trips open the line switch using automatic logic Sectionalizing Phase Loss Protection etc It turns off when the switch is closed For the normally open switch the LED...

Страница 9: ...N switch has no effect Remote Local switch Toggle this switch to the Up position to enable remote SCADA control of the line switch es and disable commands from the faceplate CLOSE OPEN switches and au...

Страница 10: ...trols most recent overcurrent fault events This information is also displayed on the OVERCURRENT FAULT Fault Magnitudes screen Maintenance Displays the software version installed in the switch control...

Страница 11: ...s Required for Lockout Shots To Lockout Time Threshold Tenths Phase Loss Protection Voltage Loss Threshold Phase Loss Protection Time Threshold Phase Loss Protection Current Threshold Automatic Reclos...

Страница 12: ...nt Transfer Capacity Left Feeder Present Transfer Capacity Right Feeder Automatic Operation Features Enabled Transfer Process Time Limit Return to Normal Delay Time Sectionalizer Reset Extended Voltag...

Страница 13: ...nt needed to operate the switch When external ac power is not available the PS IO uses power from the sensors instead if applicable When neither external ac power nor power from the sensors is availab...

Страница 14: ...ry Low message and turns on the faceplate BATTERY LOW LED At voltages below this value switch operation is still possible but only for a limited time If the calculated voltage under load drops below t...

Страница 15: ...To recharge a battery connect it to a switch control or to an independent battery charger See Table 8 in S C Specification Bulletin 1045 33 for available charger options The best approach to storing b...

Страница 16: ...setpoints such as a network address automatic operation features etc Monitor real time data such as the present line voltage and current Examine the performance and operating history of an installed s...

Страница 17: ...n of any single phase are multiplied in the summing of the phases Because there is some response latency associated with this circuitry voltage and current changes that occur within a few tenths of a...

Страница 18: ...for each sensor It also includes selection of a voltage reporting method phase to phase or phase to neutral consistent with customer transformers on the feeder and their associated step down ratios Vo...

Страница 19: ...ger than 6 82 minutes is recorded as 6 82 minutes 409 6 seconds The switch control hardware measures ground current as an analog vector sum of the three individually sensed phase currents This analog...

Страница 20: ...ruction Sheet 1041 572 for additional information The Inrush Restraint feature is applied as follows a During a voltage outage the switch control continuously monitors the switch status the RMS voltag...

Страница 21: ...t was not detected prior to the loss of voltage The control assumes the voltage loss was caused by a source side breaker or recloser opening in response to a source side overcurrent fault c The switch...

Страница 22: ...een select a combination that includes Sectionalizing STEP 2 If desired at the SETUP Automatic Operation screen set the Successful Reclose Reset Time value to coordinate with the reclosers STEP 3 Use...

Страница 23: ...led the switch control uses the following logic to determine when to reclose the switch a The switch control monitors the line for the return of all voltage phases b As soon as the switch control sens...

Страница 24: ...The feature is enabled indefinitely latched until disabled by toggling the faceplate REMOTE LOCAL switch to Remote mode When the Shots to Lockout feature is enabled a When the line switch is open If...

Страница 25: ...set to the appropriate value for this switch control STEP 2 Set the faceplate REMOTE LOCAL switch to Local mode STEP 3 Hold the faceplate automatic operation ENABLE DISABLE switch in the Enable positi...

Страница 26: ...ent look for the message with a timestamp that is older than the time for the message above it This screen includes two columns Date Time MSec This is the time to the nearest 6 25 milliseconds when th...

Страница 27: ...interrupter or recloser The control added one count to the recloser operations counter Reclose memory time limit Sequence ended Count reset The Sectionalizer Reset timer expired The switch control wil...

Страница 28: ...by a fuse or single phase recloser No OC then VL Source side SS fuse blown SS fault The switch control detected a loss of voltage on one or two phases which was not preceded by an overcurrent fault Th...

Страница 29: ...l count of the Automatic Reclose timer Because Automatic Reclose mode was enabled the control reclosed the switch No OC before VL Voltage Loss Only count reached The switch control detected a three ph...

Страница 30: ...To find the most recent event look for the message with a timestamp that is older than the time for the message above it The screen includes the following fields Date Time MSec This is the time to th...

Страница 31: ...tage rises above the Loss of Voltage Threshold setpoint The log can hold information for 16 events Once the log is full each new event over writes the oldest event in the log To find the most recent e...

Страница 32: ...shown Each DATA LOGGING Daily Highs and Lows screen shows the highest and lowest voltage and current along with associated power factor kvar and kW values for each switch for a 24 hour period 12 midni...

Страница 33: ...display the DATA LOGGING Data for Most Recent Week Menu screen click the Most Recent Week button for the desired switch if applicable at the DATA LOGGING MENU screen Data Logging for Most Recent Week...

Страница 34: ...averaged 5802 5803 controls values The switch control samples the data every 0 2 seconds It adds together eight con secutive samples and divides the total by eight to yield a 1 6 second averaged valu...

Страница 35: ...At any IntelliLink software screen click the Report Menu button STEP 3 At the REPORT MENU screen click the Full Report button to generate a report The full report includes all the information contain...

Страница 36: ...is switch control For example the default location for SNCD S0X report files is C ELine SNCD S0X The extension CFG is added automatically Note This process does not save the Physical Location on the S...

Страница 37: ...ng choose the Disconnect option from the Connection menu then choose the Close Screenset option from the File menu to clear the present screenset from memory STEP 2 From the Connection menu choose the...

Страница 38: ...4 At the SETUP MENU screen click the on the Save Data button STEP 5 In the Save Setpoints dialog box choose a file name and location for this configuration and then click on the Save button If a locat...

Страница 39: ...MUST follow the instructions described in the Updating Control Software With Battery Power Only section on page 40 Otherwise the update process will not run properly Complete the following steps to up...

Страница 40: ...properly it sets a bit on the PS IO board every few seconds If that bit goes unset for 60 seconds the PS IO board disconnects the battery shutting down the control and preventing damage to the contro...

Отзывы: