43
ENGLISH
f
K15, K16: Defrost Option
l
This is to control entering condition of defrost mode
Switch
Function
K15
K16
ON
ON
MID
ON
ON
LOW1
OFF
OFF
LOW2
❋
Defrost mode will start when the temperature difference between outdoor and outdoor heat exchanger has become
more than certain standard.
❋
Factory default status is MID. When the function changes to LOW with option control, defrost entering temperature
decreases. When defrost entering temperature decreases, the operation hour will be long but this means that the
operation hour with the reduced heating capacity increases. This option is used at places where humidity is high and the
defrost mode enters too frequently.
❋
Maintaining factory default status is recommended.
Setting the option
1. Press and hold K2 to enter the option setting. (Only available when the operation is stopped)
- If you enter the option setting, display will show the following. (If you have set the ‘Emergency operation for
compressor malfunction’, 1 or 2 will be displayed on Seg 4.)
- Seg 1 and Seg 2 will display the number for selected option.
- Seg 3 and Seg 4 will display the number for set value of the selected option.
2. If you have entered option setting, you can shortly press the K1 switch to adjust the value of the Seg 1, Seg 2 and select
the desired option. (Refer to pages 45~47 for the Seg number of the function for each option)
Example)
Z
3. If you have selected desired option, you can shortly press the K2 switch to adjust the value of the Seg 3, Seg 4 and change
the function for the selected option. (Refer to pages 45~47 for the Seg number of the function for each option)
Example)
Z