ENGLISH
t
When using A~J type of header joint, connect the header joint to the pipe with provided reducer.
t
When using K~Z type of header joint, connect the header joint to the pipe by cutting the provided reducer
properly.
t
Connect the header joint in order respecting the number of the indoor unit.
t
Connect the indoor unit as the highest capacity comes first.
10~15mm or more
CAUTION
f
Install the header joint horizontally.
- Install the header joint horizontally so that it is not facing down.
Liquid side
±10° or
less
Should be horizontal
Reducer
Header joint
Pipe
±15° or
less
Should be
horizontal
Should be horizontal
Gas side
±15° or less
Should be horizontal
±10° or less
Should be horizontal