42
Setting indoor unit option switch and key function
f
K11, K12: Changing heating capacity correction table
Switch
Function
K11
K12
ON
ON
Default
ON
OFF
Default -196 kPa
OFF
ON
Default - 98 kPa
OFF
OFF
D 98 kPa
❋
Heating operation increases frequency when current high pressure is higher than target high pressure; vice versa,
decreases frequency. When target high pressure is high, the discharge air temperature of an indoor unit will increase but
energy consumption will increase as well.
❋
Maintaining factory default status is recommended. However, if you want to reduce energy consumption or you are not
satisfied with heating performance, control the operation according to the surrounding environment. As you decrease
the target high pressure, energy consumption and noise may decrease but indoor air discharge temperature decreases
as well.
f
K13, K14: Changing current limit option table
Switch
Function
K13
K14
4 HP
5 HP
6 HP
ON
ON
Default
Default
Default
ON
OFF
Default - 4(A)
Default - 2(A)
Default - 2(A)
OFF
ON
Default - 6(A)
Default - 4(A)
Default - 4(A)
OFF
OFF
Default - 8(A)
Default - 6(A)
Default - 6(A)
Classification
Model
Default
ø1
4HP
AM040
✴
XMDEH
22A
5HP
AM050
✴
XMDEH
24A
6HP
AM060
✴
XMDEH
32A
ø3
4HP
AM040
✴
XMDGH
10A
5HP
AM050
✴
XMDGH
12A
6HP
AM060
✴
XMDGH
12A