27
ENGLISH
2. The amount of additional refrigerant for each indoor unit
(Unit : kg)
Capacity (kW)
Model
1.5
1.7
2.2
2.8
3.6
4.5
5.6
6
7.1
8.2
9
11.2 12.8
14
16
Slim 1way cassette (JSF)
(AM
✴✴✴
FN1DEH
✴
/ AM
✴✴✴
JN1DEH
✴
)
0.25 0.25 0.25
0.32
0.32
Interior 1way cassette (AM
✴✴✴
HN1DEH
✴
)
0.15 0.15
2way cassette (AM
✴✴✴
FN2DEH
✴
)
0.31
0.47
4Way Casette S (AM
✴✴✴
FN4DEH
✴
)
0.45 0.45
0.45
0.45 0.57 0.69 0.69
360 casette (AM
✴✴✴
KN4DEH
✴
)
0.45 0.45
0.45
0.45 0.69 0.69 0.69
Floor Standing Unit (AM
✴✴✴
FNFDEH
✴
)
0.22
0.32
0.32
4way cassette S (600
×
600) (AM
✴✴✴
FNNDEH
✴
)
0.29
0.29 0.29 0.29 0.37 0.37 0.37
Slim duct (AM
✴✴✴
FNLDEH
✴
)
0.17 0.17 0.17 0.26 0.35 0.35
0.45
0.42 0.42 0.62 0.62
MSP duct (AM
✴✴✴
FNMDEH
✴
)
0.24 0.24 0.24 0.28 0.28
0.28
0.32 0.54 0.68 0.68 0.91
Global duct (AM
✴✴✴
HNMPKH
✴
)
0.22 0.22 0.22
0.22
0.31 0.38 0.38 0.38
Global duct(HSP) (AM
✴✴✴
HNHPKH
✴
)
0.38 0.38 0.38
Ceiling (AM
✴✴✴
FNCDEH
✴
/ AM
✴✴✴
JNCDKH
✴
)
0.39
0.39
0.56
0.95
Console (AM
✴✴✴
FNJDEH
✴
)
0.16 0.27 0.27 0.27 0.27
Neo forte (AM
✴✴✴
FNTDEH
✴
)
0.24
0.24 0.24 0.24
0.36
0.36
Neo forte (with EEV) (AM
✴✴✴
FNQDEH
✴
)
0.34
0.34 0.34 0.34 0.51 0.51
0.51
AR5000 (AM
✴✴✴
JNADKH
✴
)
0.16
0.16 0.19 0.25 0.25 0.52
0.52 0.52
AR5000 (with EEV) (AM
✴✴✴
JNVDKH
✴
)
0.22
0.22 0.25 0.34 0.34 0.71
0.71 0.71
HSP duct (AM
✴✴✴
FNHDEH
✴
)
0.68 0.68 0.68
Boracay (AM
✴✴✴
KNTDEH)
0.24
0.24 0.32 0.32 0.49 0.49
0.49
Boracay (with EEV) (AM
✴✴✴
KNQDEH)
0.24
0.24 0.32 0.32 0.49 0.49
0.49
Ex) When the indoor unit AM022FN1DEH and AM056FN4DEH are combinated
Additional refrigerant charging = 250g + 450g = 700g
3. The total amount of additional refrigerant charging = the amount of refrigerant charging for pipe + the amount of
refrigerant for each indoor unit.
Ex) The amount of additional refrigerant charging = 3600g + 700g = 4300g
Connecting the drain hose to the outdoor unit
When using the air conditioner in the heating mode, ice may accumulate . During de-icing (defrost operation), the
condensed water must be drained off safely. Consequently, you must install a drain hose on the outdoor unit, following the
instructions below.
f
Leave space of more than 50mm between the bottom of the outdoor unit and the ground for installation of the drain
hose, as shown in figure.
f
Insert the drain plug into the hole on the underside of the outdoor unit.
f
Connect the drain hose to the drain plug.
f
Ensure that the drained water runs off correctly and safely.
13mm
50mm