![Samsung RD MHXE Series Скачать руководство пользователя страница 41](http://html1.mh-extra.com/html/samsung/rd-mhxe-series/rd-mhxe-series_installation-manual_4744181041.webp)
41
ENGLISH
f
K5: Automatic / Manual Silent mode operation setting
Switch
Function (Silent mode operation control)
K5
ON
Automatic Silent mode operation
OFF
Manual Silent mode operation
❋
You can use the Manual
Silent mode
operation, if you set the K5 DIP switch to ‘OFF’ and connect some external contact
switch to the ‘External Con’ port of MAIN PBA (shown in p.38)
f
K6: Snow prevention control option
Switch
Function (Snow prevention control)
K6
ON
Disuse snow prevention control (Default)
OFF
Use snow prevention control
❋
When you set the snow prevention control as ‘Use’, outdoor fan will operate for one minute every 30minutes in the
condition of Cooling/heating stop status at below 5°C.
f
K7, K8: Changing cooling capacity correction table
Switch
Function (Target evaporating temperature)
K7
K8
ON
ON
7 ~ 9 °C (Factory default setting)
ON
OFF
5 ~ 7 °C
OFF
ON
9 ~ 11 °C
OFF
OFF
10 ~ 12 °C
❋
Upgrade the performance by referring to the cooling long pipe performance data of the technical data book.
❋
If you upgrade the performance at your discretion, low discharge air temperature of an indoor unit might cause
discomfort. This is the option for performance correction during long pipe installation only.
f
K9, K10:
Silent mode
option. This reduces FAM RPM to operate the outdoor unit quietly during night operation.
Switch
Function (Silent mode)
K9
K10
ON
ON
Disuse Silent mode
ON
OFF
STEP - 1
OFF
ON
STEP - 2
OFF
OFF
STEP - 3
❋
Enables the silent mode for night-time in cooling mode. (It operates automatically depending on the temperature.)
❋
However, if the external contact interface module (MIM-B14) is used, entering the silent mode is available with contact
signal in cooling and heating mode.