Product Specifications
Samsung Electronics
2-39
Indoor Unit(cont.)
Q
Big Ceiling
Model
AM036JNCDCH/AA
AM048JNCDCH/AA
Power Supply
φ,V,Hz
1,208~230,60
1,208~230,60
Mode
1)
-
HP / HR
HP / HR
Performance
Capacity
Cooling
2)
Btu/h
36,000
48,000
Heating
3)
Btu/h
40,000
54,000
Power
Input Consumption (Cooling/Heating)
W
92/80
160/160
Running Current (Cooling/Heating)
A
0.94/0.83
1.45/1.45
Indoorunit refrigerant adding amount
Kg/EA
0.56
0.95
Noise Level
Actual Noise Pressure (High)
dB(A)
ײ
49
52
Fan
Type
-
Sirocco, Φ168*3EA
Sirocco, Φ168*4EA
Motor
Model
-
SIC-70CW-F1153-6,
DL-12830SSBF
(DB31-00660A)
SIC-80CW-F1244-2,
DL-12830SSBK
(DB31-00661A)
Type
-
BLDC Feedback
BLDC Feedback
Output
W
153W
244W
Airflow Rate
Fan(H/M/L)
᎑
/min
29.3/23.9/18.5
36.4/30.8/26.0
Refrigerant
Type
-
R410a
R410a
Control Method
-
EDM EEV 4.0C
EDM EEV 4.0C
Temperature Control
-
Micom&Thermistors
Micom&Thermistors
Safety Devices
-
250V/5A
250V/5A
Piping
Connections
Liquid (Flare)
Φ,mm
9.52
9.52
Φinch
3/8
͓
3/8
͓
Gas (Flare)
Φ,mm
15.88 15.88
Φinch
5/8
͓
5/8
͓
Drain
Φ,mm
VP25 (OD25,ID 20)
VP25 (OD25,ID 20)
Φinch
-
-
Weight
Net Weight
kg
33.5
42.5
Shipping Weight
kg
39.5
48.5
Dimensions
Net Dimensions (W×H×D)
mm
1350*235*675
1650*235*675
inch
-
-
Shipping Dimensions (W×H×D)
mm
1439*758*321
1739*758*321
inch
-
-
Functions
Auto Restart
-
O
O
Auto Swing
-
O
O
Group/Individual Control
-
O
O
External Contact Control
-
O
O
Trouble Shooting by LED
-
O
O
Standard
Accessories
Installation Manual
-
O
O
Operation Manual
-
O
O
Pattern Sheet for Installation
-
O
O
Flexible Drain Hose
-
O
O
Filter / Safety Grille
-
Filter (Washable)
Filter (Washable)
Optional
Accessories
Wireless Remote Controller
-
AR-DH00
AR-DH00
Wired Remote
Controller
Simplified
-
MWR-WE10N
MWR-WE10N
External Contact Interface Module
-
MIM-B14
MIM-B14
*1) Mode
- HP : Heat Pump, HR : Heat Recovery
*2) Norminal cooling capacities are based on;
- Indoor temperature : 27
ఁ
DB, 19
ఁ
WB - Outdoor temperature : 35
ఁ
DB, 24
ఁ
WB
*3) Norminal heating capacities are based on;
- Indoor temperature : 20
ఁ
DB, 15
ఁ
WB - Outdoor temperature : 7
ఁ
DB, 6
ఁ
WB
*4) Sound pressure was acquired in a dead room. Thus actual noise level may be different depending on the installation conditions.
*5) Specifications may be subject to change without prior notice for product improvement.
Содержание AM032MNQDCH/AA
Страница 343: ...PCB Diagram and Parts List Samsung Electronics 5 13 Duct type HSP Small MA 2 Drain Pump Built in cont BLDC PCB 2 3 4 1...
Страница 345: ...PCB Diagram and Parts List Samsung Electronics 5 15 Duct type BIG Duct cont EMI PCB 1 2 3 5 4...
Страница 347: ...PCB Diagram and Parts List Samsung Electronics 5 17 5 1 6 Celing type 1 2 3 4 5 6 7 19 18 9 10 11 12 17 15 14 13 8...
Страница 364: ...PCB Diagram and Parts List 5 34 Samsung Electronics OAP DUCT AM6JNESCH AA cont BLDC Driver PCB 6 5 4 3 2 1...
Страница 378: ...PCB Diagram and Parts List 5 48 Samsung Electronics 5 1 16 360 cassette MAIN PCB 1 2 3 4 5 6 7 8 9 10 11 12 13...
Страница 384: ...Wiring Diagram Samsung Electronics 6 3 6 1 3 BIG Duct This Document can not be used without Samsung s authorization...
Страница 385: ...Wiring Diagram 6 4 Samsung Electronics 6 1 4 Ceiling This Document can not be used without Samsung s authorization...
Страница 387: ...Wiring Diagram 6 6 Samsung Electronics 6 1 6 RAC Neo Forte This Document can not be used without Samsung s authorization...
Страница 393: ...6 12 Samsung Electronics 6 1 12 OAP Duct type This Document can not be used without Samsung s authorization...
Страница 394: ...Samsung Electronics 6 13 6 1 13 Wall Mounted type Boracay This Document can not be used without Samsung s authorization...