Troubleshooting
Samsung Electronics
4-11
- Setting an indoor unit address and installation option
Ŷ
Setting an indoor unit installation option (suitable for the condition of each installation location
)
1. Check whether power is supplied or not.
-
When the indoor unit is not plugged in, there should be additional power supply
in the indoor unit.
2. The panel(display ) should be connected to an indoor unit to receive option.
3. Set the installation option according to the installation condition of an air
conditioner.
- The default setting of an indoor unit installation option is 020010-100000-200000-300000.
- Individual control of a remote controller(SEG20) is the function that controls an indoor unit individually when there is more
than one indoor unit.
4. Set the indoor unit option by wireless remote controller.
SEG1
SEG2
SEG3
SEG4
SEG5
SEG6
0
2
RESERVED
External room
temperature sensor
/ Minimizing fan
operation when
themostat is off
Central control
FAN RPM
compensation
SEG7
SEG8
SEG9
SEG10
SEG11
SEG12
1
Drain pump
Hot water heater
Electronic heater
Opening the
electronic expansion
valve
Master / Slave
SEG13
SEG14
SEG15
SEG16
SEG17
SEG18
2
External control
External control
output / External
heater On or off signal
S-Plasma ion
Buzzer
Number of hours
using filter
SEG19
SEG20
SEG21
SEG22
SEG23
SEG24
3
Individual control of a
remote controller
Heating setting
compensation
EEV opening of an
indoor unit stopped
during oil return or
Defrost operation.
-
Human sensor
▶
1WAY/2WAY/4WAY MODEL : Drain pump(SEG8) will be set to 'USE + 3minute delay' even if the drain pump is set to 0.
▶
1 WAY/2WAY/4WAY,DUCT MODEL : Number of hours using filter(SEG18) will be set to '1000hour' even if the SEG18 is set to
exept for 2 or 6.
▶
If you input a number other than 0~4 of the individual control of the indoor unit(SEG20), the indoor is set as indoor 1.
▶
SEG5 central control option is basically set as 1 (Use), so you don’t need to set the central control option additionally.
However, if the central control is not connected but it doesn’t indicate an error message, you need to set the central control
option as 0 (Disuse) to exclude the indoor unit from the central control.
▶
The output of hot water heater in SEG9 is generated from the hot coil part of the terminal board in duct models.
F4
F3
F1
F2
V2
V1
1(L) 2(N)
2
1
HOT
COIL
AC
POWER
OUTDOOR COM-
MUNICATION
Wire Remote
Controller
DC 12 V
* The output of hot coil terminal is AC 220 V / 230 V
(The same as Indoor Unit’s input Power)
COM1 COM2
(+) L
N
(-)
▶
The external output of SEG15 is generated by MIM-B14 connection. (Refer to the manual of MIM-B14.)
Indoor Unit
1(L)
F2
F1
2(N)
Содержание AM032MNQDCH/AA
Страница 343: ...PCB Diagram and Parts List Samsung Electronics 5 13 Duct type HSP Small MA 2 Drain Pump Built in cont BLDC PCB 2 3 4 1...
Страница 345: ...PCB Diagram and Parts List Samsung Electronics 5 15 Duct type BIG Duct cont EMI PCB 1 2 3 5 4...
Страница 347: ...PCB Diagram and Parts List Samsung Electronics 5 17 5 1 6 Celing type 1 2 3 4 5 6 7 19 18 9 10 11 12 17 15 14 13 8...
Страница 364: ...PCB Diagram and Parts List 5 34 Samsung Electronics OAP DUCT AM6JNESCH AA cont BLDC Driver PCB 6 5 4 3 2 1...
Страница 378: ...PCB Diagram and Parts List 5 48 Samsung Electronics 5 1 16 360 cassette MAIN PCB 1 2 3 4 5 6 7 8 9 10 11 12 13...
Страница 384: ...Wiring Diagram Samsung Electronics 6 3 6 1 3 BIG Duct This Document can not be used without Samsung s authorization...
Страница 385: ...Wiring Diagram 6 4 Samsung Electronics 6 1 4 Ceiling This Document can not be used without Samsung s authorization...
Страница 387: ...Wiring Diagram 6 6 Samsung Electronics 6 1 6 RAC Neo Forte This Document can not be used without Samsung s authorization...
Страница 393: ...6 12 Samsung Electronics 6 1 12 OAP Duct type This Document can not be used without Samsung s authorization...
Страница 394: ...Samsung Electronics 6 13 6 1 13 Wall Mounted type Boracay This Document can not be used without Samsung s authorization...