Troubleshooting
Samsung Electronics
4-43
غ
Diagnosis and Adjustment (Error Code)
ـ
Error code related to the Communications / Settings / HW
(cont.)
CODE
Explanation
E-311
Error on temperature sensor of double layer pipe/liquid pipe(sub heat exchanger) (Short or Open)
E-321
Error on EVI (ESC) IN temperature sensor (Short or Open)
E-322
Error on EVI (ESC) OUT temperature sensor (Short or Open)
E-323
Error on suction sensor 2 (Short or Open)
E-346
Error due to operation failure of Fan2
E-347
Motor wire of Fan2 is not connected
E-348
Lock error on Fan2 of outdoor unit
E-353
Error due to overheated motor of outdoor unit's Fan2
E-355
Error due to overheated IPM of Fan2
E-361
Error due to operation failure of inverter compressor 2
E-364
Error due to over-current of inverter compressor 2
E-365
V-limit error of inverter compressor 2
E-366
Error due to over voltage /low voltage of inverter PBA2
E-367
Error due to unconnected wire of compressor 2
E-368
Output current sensor error of inverter PBA2
E-369
DC voltage sensor error of inverter PBA2
E-374
Heat sink temperature sensor error of inverter PBA2
E-378
Error due to overcurrent of Fan2
E-385
Error due to input current of inverter 2
E-386
Over-voltage/low-voltage error of Fan2
E-387
Hall IC connection error of Fan2
E-389
V-limit error on Fan2 of compressor
E-393
Output current sensor error of Fan2
E-396
DC voltage sensor error of Fan2
E-399
Heat sink temperature sensor error of Fan2
E-400
Error due to overheat caused by contact failure on IPM of Inverter PBA2
E-407
Compressor operation stop due to high pressure protection control
E-410
Compressor operation stop due to low pressure protection control or refrigerant leakage
E-416
Compressor operation stop due to discharge temperature protection control
E-425
Phase reversal or phase failure (3Ø outdoor unit wiring, R-S-T-N ), connection error on 3 phase
input
E-428
Compressor operation stop due abnormal compression ratio
E-438
EVI (ESC) EEV leakage or internal leakage of intercooler or incorrect connector insertion of EVI
(ESC) EEV
E-439
Error due to refrigerant leakage
E-440
Heating mode restriction due to high air temperature
E-441
Cooling mode restriction due to low air temperature
E-442
Refrigerant charing restriction in heating mode when air temperature is over 15 °C
E-443
Operation prohibited due to low pressure
E-445
CCH is deatched
E-446
Error due to operation failure of Fan1
Содержание AM032MNQDCH/AA
Страница 343: ...PCB Diagram and Parts List Samsung Electronics 5 13 Duct type HSP Small MA 2 Drain Pump Built in cont BLDC PCB 2 3 4 1...
Страница 345: ...PCB Diagram and Parts List Samsung Electronics 5 15 Duct type BIG Duct cont EMI PCB 1 2 3 5 4...
Страница 347: ...PCB Diagram and Parts List Samsung Electronics 5 17 5 1 6 Celing type 1 2 3 4 5 6 7 19 18 9 10 11 12 17 15 14 13 8...
Страница 364: ...PCB Diagram and Parts List 5 34 Samsung Electronics OAP DUCT AM6JNESCH AA cont BLDC Driver PCB 6 5 4 3 2 1...
Страница 378: ...PCB Diagram and Parts List 5 48 Samsung Electronics 5 1 16 360 cassette MAIN PCB 1 2 3 4 5 6 7 8 9 10 11 12 13...
Страница 384: ...Wiring Diagram Samsung Electronics 6 3 6 1 3 BIG Duct This Document can not be used without Samsung s authorization...
Страница 385: ...Wiring Diagram 6 4 Samsung Electronics 6 1 4 Ceiling This Document can not be used without Samsung s authorization...
Страница 387: ...Wiring Diagram 6 6 Samsung Electronics 6 1 6 RAC Neo Forte This Document can not be used without Samsung s authorization...
Страница 393: ...6 12 Samsung Electronics 6 1 12 OAP Duct type This Document can not be used without Samsung s authorization...
Страница 394: ...Samsung Electronics 6 13 6 1 13 Wall Mounted type Boracay This Document can not be used without Samsung s authorization...