Troubleshooting
4-24
Samsung Electronics
Option
SEG13 SEG14 SEG15 SEG16 SEG17
SEG18
(*3)
Explanation
Control variables when using hot water /
external heater
Remote Controller
Display
Indication and Details
Indication
Details
Set temp. for
heater On/Off
Delay time
for heater
On
0
At the same
time as thermo
on
No delay
1
At the same
time as thermo
on
10 minutes
2
At the same
time as thermo
on
20 minutes
3
2.7 °F
(1.5 °C)
No delay
4
2.7 °F
(1.5 °C)
10 minutes
5
2.7 °F
(1.5 °C)
20 minutes
6
5.4 °F
(3.0 °C)
No delay
7
5.4 °F
(3.0 °C)
10 minutes
8
5.4 °F
(3.0 °C)
20 minutes
9
8.1 °F
(4.5 °C)
No delay
A
8.1 °F
(4.5 °C)
10 minutes
B
8.1 °F
(4.5 °C)
20 minutes
C
10.8 °F
(6.0 °C)
No delay
D
10.8 °F
(6.0 °C)
10 minutes
E
10.8 °F
(6.0 °C)
20 minutes
(*1) Height difference : The difference of the height between the corresponding indoor uint and the indoor unit installed at the lowest
place.
For example, When the indoor unit is installed 40 m(131.23 ft) higher than the indoor unit installed at the lowest
place, select the option 1.
(*2) Distance : The difference between the pipe length of the indoor unit istalled at farthest place from an outdoor unit and the pipe
length of the corresponding indoor unit from an outdoor unit.
For example, when the farthest pipe length is 100 m(328 ft) and the corresponding indoor unit is 40 m(131.23 ft) away
from an outdoor unit, select the option 2.
(100 m(328 ft) - 40 m(131.23 ft) = 60 m(196.85 ft))
(*3) Heater operation when the SEG9 of 02 series installation option is set to using hot water heater or when SEG15 is set to using
external heater
e.g. 1) Setting 02 series SEG9 =1 / Setting 05 series SEG18 = 0: Hot water heater is turned on at the same time as the heating ther-
mostat is on, and turned off when the heating thermostat is off.
e.g. 2) Setting 02 series SEG15 =2 / Setting 05 series SEG18 =A:
Room temp. ≤ set temp. + f(heating compensation temp.)
- External heater is turned on when the temperature is maintained as 8.1 °F(4.5 °C) for 10 minutes.
Room temp. > set temp. + f(heating compensation temp.)
- External heater is turned off when the temperature is maintained as 8.1 °F(4.5 °C) + 1.8 °F(1 °C)
(1 °C is the Hysteresis for On/Off selection.)
Содержание AM032MNQDCH/AA
Страница 343: ...PCB Diagram and Parts List Samsung Electronics 5 13 Duct type HSP Small MA 2 Drain Pump Built in cont BLDC PCB 2 3 4 1...
Страница 345: ...PCB Diagram and Parts List Samsung Electronics 5 15 Duct type BIG Duct cont EMI PCB 1 2 3 5 4...
Страница 347: ...PCB Diagram and Parts List Samsung Electronics 5 17 5 1 6 Celing type 1 2 3 4 5 6 7 19 18 9 10 11 12 17 15 14 13 8...
Страница 364: ...PCB Diagram and Parts List 5 34 Samsung Electronics OAP DUCT AM6JNESCH AA cont BLDC Driver PCB 6 5 4 3 2 1...
Страница 378: ...PCB Diagram and Parts List 5 48 Samsung Electronics 5 1 16 360 cassette MAIN PCB 1 2 3 4 5 6 7 8 9 10 11 12 13...
Страница 384: ...Wiring Diagram Samsung Electronics 6 3 6 1 3 BIG Duct This Document can not be used without Samsung s authorization...
Страница 385: ...Wiring Diagram 6 4 Samsung Electronics 6 1 4 Ceiling This Document can not be used without Samsung s authorization...
Страница 387: ...Wiring Diagram 6 6 Samsung Electronics 6 1 6 RAC Neo Forte This Document can not be used without Samsung s authorization...
Страница 393: ...6 12 Samsung Electronics 6 1 12 OAP Duct type This Document can not be used without Samsung s authorization...
Страница 394: ...Samsung Electronics 6 13 6 1 13 Wall Mounted type Boracay This Document can not be used without Samsung s authorization...