Setting an indoor unit address and installation option
(*3)
Heater operation when the SEG9 of 02 series installation option is set to using heater
e.g. 1) Setting 02 series SEG9 =”1” / Setting 05 series SEG18 = “0”: heater is turned on at the same time as the heating
thermostat is on, and turned off when the heating thermostat is off.
e.g. 2) Setting 02 series SEG15 =”2” / Setting 05 series SEG18 =”A”: Room temp. ≤ set temp. + f (heating compensation temp.)
‐
Heater is turned on when the temperature is maintained as 8.1 °F (4.5 °C) for 10 minutes.
Room temp. > set temp. + f (heating compensation temp.)
‐
Heater is turned off when the temperature is maintained as 8.1 °F(4.5 °C )+1.8 °F(1 °C ) [1.8 °F(1 °C ) is the
Hysteresis for On/Off selection.]
SEG 3, 4, 5, 6, 8, 9 additional information
When the SEG 3 is set as “1” and follow Auto Change Over for HR only operation, it will operate as follows.
Cool
ing Th
ermo Off
He
ating Th
ermo Off
Cool
ing Th
ermo On
He
ating Th
ermo On
B
C
D
Ts
A
c
a
Temp.
d
b
Standard temp.
for Heating
Standard temp.
for Cooling
Standard temp. for
Heating
→
Cooling
Standard temp.
for Cooling
→
Heating
Set temp.
for Auto mode
A : Set with SEG4(˚C)
B : Set with SEG5(˚C)
C : Set with SEG6(˚C)
D : Set with SEG8(˚C)
Cooling/Heating mode can be changed when Thermo Off status is maintained during the time with SEG9.
AM072TNZDCH_IM_DVM V-AHU_AA_EN_.indd 42
2020-02-14 오전 10:33:41
Содержание AM0 SERIES
Страница 45: ...45 English Appendix Memo AM072TNZDCH_IM_DVM V AHU_AA_EN_ indd 45 2020 02 14 오전 10 33 41 ...
Страница 46: ...AM072TNZDCH_IM_DVM V AHU_AA_EN_ indd 46 2020 02 14 오전 10 33 41 ...
Страница 91: ...45 Français Annexe Note AM072TNZDCH_IM_DVM V AHU_AA_FR_ indd 45 2020 02 14 오전 10 35 49 ...
Страница 92: ...AM072TNZDCH_IM_DVM V AHU_AA_FR_ indd 46 2020 02 14 오전 10 35 49 ...