![Samsung AM0 SERIES Скачать руководство пользователя страница 36](http://html.mh-extra.com/html/samsung/am0-series/am0-series_installation-manual_336812036.webp)
36
English
Instal
lation
Step 5. Check operation
1. Set the indoor unit address and installation option with remote controller option. Set the each option separately
since you cannot set the ADDRESS setting and indoor unit installation setting option at the same time. You need to
set twice when setting indoor unit address and installation option.
2. Take the batteries out of the remote controller to exit programming mode and insert them again and then press the operation button.
3. Reset Indoor Unit after option code programming.
Setting an indoor unit address (MAIN/RMC)
1. Check whether power is supplied or not.
‐
When the indoor unit is not plugged in, there should be additional power supply in the indoor unit.
2. Before installing the indoor unit, assign an address to the indoor unit according to the air conditioning system plan.
3. Assign an indoor unit address by wireless remote controller.
‐
The initial setting status of indoor unit ADDRESS(MAIN/RMC) is
“0A0000-100000-200000-300000” (address: 00, RMC1: 0, RMC2: 0).
Option No. : 0AXXXX-1XXXXX-2XXXXX-3XXXXX
Option
SEG1
SEG2
SEG3
SEG4
SEG5
SEG6
Explanation
PAGE
MODE
Setting Main address 100-digit of indoor
unit address
10-digit of indoor
unit
The unit digit of an
indoor unit
Indication
and Details
Indication Details Indication Details Indication Details Indication Details Indication Details Indication Details
0
A
0
No Main
address
0~9
100 -digit
0~9
10 -digit
0~9
A unit
digit
1
Main
address
setting
mode
Option
SEG7
SEG8
SEG9
SEG10
SEG11
SEG12
Explanation
PAGE
-
Setting RMC address
-
Group channel(*16)
Group address
Indication
and Details
Indication Details
-
Indication Details
-
Indication Details Indication Details
1
0
No RMC
address
RMC1
0~F
RMC2
0~F
1
RMC
address
setting
mode
CAUTION
•
When “A”~”F” is entered to SEG5~6, the indoor unit MAIN ADDRESS is not changed.
•
If you set the SEG 3 as 0, the indoor unit will maintain the previous MAIN ADDRESS even if you input the option value of SEG5~6.
•
If you set the SEG 9 as 0, the indoor unit will maintain previous RMC ADDRESS even if you input the option value of SEG11~12.
•
You cannot set SEG11 and SEG12 as F value at the same time.
Setting an indoor unit address and installation option
AM072TNZDCH_IM_DVM V-AHU_AA_EN_.indd 36
2020-02-14 오전 10:33:40
Содержание AM0 SERIES
Страница 45: ...45 English Appendix Memo AM072TNZDCH_IM_DVM V AHU_AA_EN_ indd 45 2020 02 14 오전 10 33 41 ...
Страница 46: ...AM072TNZDCH_IM_DVM V AHU_AA_EN_ indd 46 2020 02 14 오전 10 33 41 ...
Страница 91: ...45 Français Annexe Note AM072TNZDCH_IM_DVM V AHU_AA_FR_ indd 45 2020 02 14 오전 10 35 49 ...
Страница 92: ...AM072TNZDCH_IM_DVM V AHU_AA_FR_ indd 46 2020 02 14 오전 10 35 49 ...