![Samsung AM0 SERIES Скачать руководство пользователя страница 26](http://html.mh-extra.com/html/samsung/am0-series/am0-series_installation-manual_336812026.webp)
26
English
Wiring Work
Instal
lation
Example of Installation
‐
Total power cable length L = 328 ft(100 m), Running current of each units 1[A]
‐
Total 10 indoor units were installed
or
•
Apply following equation.
Coef×35.6×L
k
×i
k
※
Calculation
10 % of input
Voltage [V]
n
Σ
k=1
(
) <
1000×A
k
•
Installing with 1 sort wire.
•
Installing with 2 different sort wire.
ELCB
10[A]
9[A]
1[A]
Indoor unit 10
Indoor unit 1
0 ft (0 m)
32 ft (10 m)
65.6 ft (20 m)
328 ft (100 m)
Indoor unit 2
MCCB+
ELB
0.0039 inch² (2.5mm²)
0.0062 inch² (4.0mm²) 0.0062 inch² (4.0mm²)
············ 0.0062 inch² (4.0mm²) ············
220 [V]
-2.2 [V]
-1.4 [V]
-(1.4+1.2+1.8+1.5+1.3+1.1+0.9+0.7+0.4+0.2)=-10.5[V]
209.5 [V] (Within 187 V ~ 253V)
it's okay
-1.2 [V]
-2.0 [V]
220 [V]
-(2.2+2.0+1.8+1.5+1.3+1.1+0.9+0.7+0.4+0.2)=-11.2[V]
208.8 [V](Within 187 V ~ 253 V)
it's okay
0.0039 inch² (2.5mm²) ············ 0.0039 inch² (2.5mm²) ············
AM072TNZDCH_IM_DVM V-AHU_AA_EN_.indd 26
2020-02-14 오전 10:33:35