Functions
WE
Configuration
Storage tank sensor SF1
1
CO4 -> F01 - 1
Thermal disinfection
0
3
0:00h
4:00h
70 °C
10 °C
0 °C
1
CO4 -> F14 - 1
Day of the week / 1–7, 1, 2, ..., 7 with
1–7 = every day, 1 = Monday, ..., 7 = Sunday
Start time / 0:00h to 23:45h; in steps of 15 minutes
Stop time / 0:00h to 23:45h; in steps of 15 minutes
Disinfection temperature / 60 to 90 °C
Set point boost / 0 to 50 °C
Hold time of disinfection temperature / 0 to 255 °C
bE = 1, 0 (start of disinfection with BE17 = ON, OFF;
only applies when Start time = Stop time)
94
EB 5579 EN
Functions of the DHW circuit