Proceed as follows:
Switch to configuration and parameter level.
Display shows:
0 0 0 0
q
Set valid key number.
Confirm key number.
Display shows:
PA1
q
Select parameter level (-> Fig. 2).
Open parameter level.
q
Select desired parameter.
Activate editing mode for the parameter.
q
Edit the parameter.
Confirm the parameter.
To adjust additional parameters, repeat the steps in the fields highlighted in gray.
q
Select
End
.
Exit parameter level.
q
Select
End
.
Return to the operating level.
2.4
Calibrating the sensors
The connected sensors are calibrated in CO5 configuration level.
The following applies:
4
CO5 -> F01 - 1, CO5 -> F02 - 0, CO5 -> F03 - 0: Pt 1000 (Pt 100) sensors (default)
4
CO5 -> F01 - 0, CO5 -> F02 - 0, CO5 -> F03 - 0: PTC (Pt 100) sensors
4
CO5 -> F01 - 0, CO5 -> F02 - 1, CO5 -> F03 - 0: NTC (Pt 100) sensors
4
CO5 -> F01 - 1, CO5 -> F02 - 1, CO5 -> F03 - 0: Ni 1000 (Pt 100) sensors
4
CO5 -> F01 - 0, CO5 -> F02 - 0, CO5 -> F03 - 1: Pt 500 (Pt 100) sensors
The resistance values of the sensors can be found on page 163.
If the temperature values displayed at the controller differ from the actual temperatures, the
measured values of all connected sensors can be changed or readjusted. To calibrate a sen-
sor, the currently displayed sensor value must be changed such that it matches the tempera-
ture (reference temperature) measured directly at the point of measurement.
EB 5579 EN
25