Solar pump OFF
0 to 30 °C
Max. storage tank temperature
20 to 90 °C
Function block parameters (CO4)
Level 4
Range of values
Limiting factor (F03 - 1)
0.1 to 10.0
Stop parallel operation in case of deviation (F06 - 1)
0 to 10 min
Flow limit temp. for parallel pump operation (F06 - 1)
20 to 90 °C
Activate priority in case of deviation (F08 - 1)
2 to 10 min
Correction factor (F08 - 1)
0.1 to 10.0
Activate priority in case of deviation (F09 - 1)
2 to 10 min
Proportional gain K
P
(F12 - 1)
0.1 to 50
Reset time T
N
(F12 - 1)
1 to 999 sec
Derivative-action time T
V
(F12 - 1)
0 to 999 sec
Valve transit time T
Y
(F12 - 1)
5 to 240 sec
Hysteresis (F12 - 0)
1 to 30 °C
Min. ON time (F12 - 0)
0 to 10 min
Min. OFF time (F12 - 0)
0 to 10 min
Max. deviation (F13 - 1)
2 to 10 °C
Day of the week (F14 - 1)
1–7, 1 to 7
Start time (F14 - 1)
0:00h to 23:45h
Stop time (F14 - 1)
0:00h to 23:45h
Disinfection temperature (F14 - 1)
60 to 90 °C
Set point boost (F14 - 1)
0 to 50 °C
Hold time of disinfection temperature (F14 - 1)
0 to 255 min
Parameters in level 5
Parameters (PA5)
Level 5
Range of values
Public holidays
01.01 to 31.12