Parameters in level 6
Parameters (PA6)
Level 6
Range of values
Station address (ST-NR)
1
1
to 247
to 32000
Baud rate (BAUD)
9600, 19200
Cyclical initialization (I)
1 to 255 min
Modem dialing pause (P)
0 to 255 min
Modem time-out (t)
1 to 255 min
Number of redialing attempts (C)
1 to 255
Phone no. of control station (tELnr)
–
Access number (tAPnr)
–
Mobile phone number (HAndy)
–
Function block parameters (CO6)
Level 6
Range of values
Meter bus address WMZ1 to WMZ6 (F10 - 1)
0 to 255
Model code WMZ1 to WMZ6 (F10 - 1)
APAtO, CAL3,
1434, SLS
Reading mode WMZ1 to WMZ6 (F10 - 1)
COIL, 24h, CONT
Max. limit value (F11 - 1)
0.01 to 650
m
h
3
Max. limit value for heating (F11 - 1)
0.01 to 650
m
h
3
Max. limit value for DHW (F11 - 1)
0.01 to 650
m
h
3
Limiting factor (F11 - 1)
0.1 to 10
Max. limit value (F12 - 1)
0.1 to 6500 kW
Max. limit value for heating (F12 - 1)
0.1 to 6500 kW
Max. limit value for DHW (F12 - 1)
0.1 to 6500 kW
Limiting factor (F12 - 1)
0.1 to 10
EB 5579 EN
171
Appendix