F Function
WE
Anl
Comment
Function block parameters
/ Range of values (default)
17 Processing of
external demand,
binary
Input term. 17/18
0
Not in
systems
with solar
circuit or
room panel
RF3/FG3
CO1 -> F17 - 1: Only with
•
CO1 -> F15 - 1
•
CO1 -> F16 - 0
Options
bE / 1, 0 (1)
18 Request max. flow
set point over a
0 to 10 V signal
0
All
CO1 -> F18 - 1: Controller output Y1 no longer available.
The max. flow set point is requested as a 0 to 10 V signal
over Y1.
Function block parameters:
Lower transmission range / 0 to 130 °C (0 °C)
Upper transmission range / 0 to 130 °C (120 °C)
F Function block number, WE Default value, Anl System code number
CO2: Heating circuit Rk2
(systems Anl 3.0-3.4, 4.x, 5.x, 6.0, 10.x and 25.0)*
F Function
WE
Anl
Comment
Function block parameters
/ Range of values (default)
01 Room sensor RF2
0
All*
CO2 -> F01 - 1: Temperature display and input FG2 for
Type 5244/5257-5 Room Panel active
TROVIS 5570 Room Panel:
CO2 -> F01 - 1
and
CO7 -> F04 - 1
02 Outdoor sensor
AF2
0
4.x, 5.x,
6.0, 10.x,
25.0
Without measured value AF2, the value of AF1 is read
Outdoor temperature received via device bus:
CO2 -> F02 - 1
and
CO7 -> F09 - 1
03 Return flow sensor
RüF2
1
10.0,
25.0
CO2 -> F03 - 1: Sensor and limiting function active
Function block parameter:
Limiting factor / 0.1 to 10.0 (1.0)
0
3.x, 4.x,
5.x, 6.0
10.1-10.3
04 Reserved
EB 5579 EN
135
Appendix