Systems Anl 1.1 to 1.4
System
Anl 1.1
Anl 1.2
Anl 1.3
Anl 1.4
Type of DHW heating
Type 1
Type 2
Type 3
Type 4
1)
XX =
SLP
UP2
SLP
UP2
Integration of flow sensor VF4
Possible
Possible
Possible
Possible
ZP integration with CO4 ->
F10 - 1 (broken line, see cover)
–
Not possible
–
Not possible
Note
–
Only
second-
ary system
–
Only
second-
ary system
Default settings
CO1 -> F01
- 0 (w/o RF1)
- 0 (w/o RF1)
- 0 (w/o RF1)
- 0 (w/o RF1)
CO1 -> F02
- 1 (with AF1)
- 1 (with AF1)
- 1 (with AF1)
- 1 (with AF1)
CO1 -> F03
- 1 (with RüF1) - 0 (w/o RüF1) - 1 (with RüF1) - 0 (w/o RüF1)
CO4 -> F01
- 1 (with SF1)
- 1 (with SF1)
- 1 (with SF1)
- 1 (with SF1)
CO4 -> F02
- 0 (w/o SF2)
- 1 (with SF2)
- 0 (w/o SF2)
- 1 (with SF2)
CO4 -> F05
- 0 (w/o VF4)
- 0 (w/o VF4)
- 0 (w/o VF4)
- 0 (w/o VF4)
32
EB 5579 EN
Systems
UP1
XX
1)
AF1
RK1/Y1 VF1
RüF1 RF1
BE
BA
AE
AA
DHW
heating