EB 8389 EN
115
Appendix
Code
No.
Parameter
– Readings/
values [default setting]
Description
Codes with marked with an asterisk (*) must be enabled with Code
3
prior to configuration.
49* h5
Operating point limit
55.0 to 100.0 % of
reference variable,
[75.0 %]
Types 3730-2/-3 and Type 3731-3 only
Valve is moved to the operating point when the operating point limit
is exceeded.
h6
Unassigned
h7
Limit value travel anal-
ysis
[0.6] to 30.0 s
Types 3730-2/-3 and Type 3731-3 only
Time limit for difference between reference value and currently re-
corded value. Determines the difference at which a message is gen-
erated.
h8
Limit value time analy-
sis
0.1 to 100.0 % of the
valve position, [0.3 %]
Types 3730-2/-3 and Type 3731-3 only
Travel limit for difference between reference value and currently re-
corded value. Determines the difference at which a message is gen-
erated.
h9
Status classification for
on/off
C
Maintenance required
OK No message
CR Maintenance demanded
b
Maintenance alarm
S
Out of specification
Read only
9.1.1
PROFIBUS parameter (Type 3730-4)
Code
No.
Parameter
– Readings/
values [default setting]
Description
Codes with marked with an asterisk (*) must be enabled with Code 3 prior to configuration.
48* F0
Firmware rev.
Communication
F1
Binary input 1
0
Not active
1
Active
F2
Binary input 2
0
Not active
1
Active