64
EB 8389 EN
Tests
1.
Settings > Identification > Positioner > Actu
-
ator
−
Model:
Single acting, [-/-]
2.
−
Booster:
Not present, [-/-]
Defining parameters
1. Switch to manual mode.
2.
Select classification for status messages.
3. Start test.
The 'Test information' status indicates
'Running test'. 'd1' and 'tEST' are indi-
cated in alternating sequence on the po-
sitioner display.
'Function check' is activated as the
condensed state.
1.
Operation > Operating mode
1)
Target mode (Code 0): Manual
Types 3730-2/-3/-4/-5 (1.5x) and Type 3731-3:
2.
Settings > Positioner > Error control > Classi-
fication report > Extended > ...
Air supply
−
Perhaps modified (TEST):
[ ], , , ( ), ( )
−
Perhaps not enough (TEST):
[ ], , , ( ), ( )
−
Working at full capacity (TEST):
[ ], , , ( ), ( )
Leakage pneumatics
−
Perhaps existing (TEST):
[ ], , , ( ), ( )
−
Perhaps too large (TEST):
[ ], , , ( ), ( )
Actuator springs
−
Spring stiffness may be reduced (spring fail-
ure) (TEST): [ ], , , ( ), ( )
−
Perhaps bias reduced (TEST):
[ ], , , ( ), ( )
−
Working at full capacity (TEST):
[ ], , , ( ), ( )
Type 3730-5 (1.6x) and Type 3731-5:
2.
Settings > Positioner > Diagnosis
configuration > Classification
−
Air supply: [ ], , , ,
−
Leakage pneumatics: [ ], , , ,
−
Actuator springs: [ ], , , ,
3. Start test
1)
Types 3730-4/-5 and Type 3731-5: Opera
-
tion > Operating mode > Positioner (AO,
TRD)
Cancel the test by right-clicking 'Stop test'
and selecting 'Execute' or by pressing the ro
-
tary pushbutton at the positioner.
After the test has been canceled, the posi-
tioner remains in manual mode.
In TROVIS-VIEW the test information and
progress flag of the test are displayed. The
'Test information' status indicates 'Test fin
-
ished' after the test is finished.
Every time the test is performed, old mea
-
sured data are overwritten (Repetition).
Note
Note