126
EB 8389 EN
Appendix
Message
Possible reasons
Recommended action
Status
classifica
-
tion
Single reset
Open/Close
−
The breakaway time or
transit time differs from the
reference value by the
amount entered in 'Limit
value travel analysis'.
−
The valve end position
differs from the reference
value by the amount
entered in 'Limit value
travel analysis'.
−
The end position cannot be
reached.
−
Check that pneumatic
installations and
connections are tight.
−
Check supply pressure.
−
Check plug stem for
external influences that
could be blocking it.
•
[ ]
•
Section 4.1.3
9.3 Diagnostic data points saved in a non-volatile memory
Data saved in a non-volatile memory:
Saved directly after they change
Saved cyclically every 24 h
Statistical information
Open/Close
'Limit value time analysis', 'Limit value travel
analysis'.
Reference assessment
Assessment
Data logger
'Selection', 'Trigger status', 'Scan rate',
'Trigger value', 'Trigger band', 'Trigger
edge', 'Pre-trigger time', 'Trigger via con-
densed state'
Valve position x histogram
Measured values
Short-term monitoring
Scan rate, short-term histogram
Set point deviation e histogram
Measured values
Short-term monitoring
Scan rate, short-term histogram
Cycle counter histogram
Measured values
Short-term monitoring
Drive signal diagram steady-state
Measured values
Short-term monitoring
Measured values
Drive signal diagram hysteresis (d5)
'Start test', 'Enable time distance', 'Min. time
distance from test', 'Tolerance band of hys-
teresis'
Measured values
Содержание TROVIS 3730-3
Страница 6: ...6 EB 8389 EN...
Страница 43: ......
Страница 57: ......
Страница 83: ...EB 8389 EN 83...
Страница 130: ...130 EB 8389 EN...